B.2 Parameter Tables
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
171
B
U2-58
(847H)
Power Supply 
Frequency at 
Previous Fault
AC 
Frequency 
Shows the frequency on the power supply side.
No signal 
output 
available
0.1 Hz
U2-59
(848H)
Power Supply 
Side Current 
Reference at 
Previous Fault
AC Current 
Ref 
Shows the current reference on the power supply side when the most 
recent fault occurred.
No signal 
output 
available
1 A
U2-60
(849H)
Power Factor at 
Previous Fault
Power 
Factor 
Shows the power factor when the most recent fault occurred.
No signal 
output 
available
1%
U2-61
(84AH)
Active Current 
Reference at 
Previous Fault
Active 
Current 
Shows the active current when the most recent fault occurred.
No signal 
output 
available
0.1%
U2-62
(84BH)
Reactive Current 
Reference at 
Previous Fault
Reactive 
Current 
Shows the reactive current when the most recent fault occurred.
No signal 
output 
available
0.1%
U2-63
(84CH)
DC Bus Voltage 
Reference at 
Previous Fault 
(After SFS)
DC V SFS 
Level 
Shows the DC bus voltage reference after the soft starter.
No signal 
output 
available
1 V
U2-64
(84DH)
Avr Input 
(Voltage 
Deviation) at 
Previous Fault
AVR Input Shows the Avr input.
No signal 
output 
available
1 V
U2-65
(84EH)
Control Voltage 
Reference (Vq) at 
Previous Fault
Voltage Ref 
(Vq) 
Shows the control voltage reference (Vq) when the most recent fault 
occurred.
No signal 
output 
available
1 V
U2-66
(84FH)
Control Voltage 
Reference (Vd) at 
Previous Fault
Voltage Ref 
(Vd) 
Shows the control voltage reference (Vd) when the most recent fault 
occurred.
No signal 
output 
available
1 V
U3: Fault History
U3-01 to
U3-04
(90H to
93H)
First to 4th Most 
Recent Fault
Fault 
Message 
Displays the first to the fourth most recent faults.
No signal 
output 
available
–
U3-05 to
U3-10
(804H to
809H)
5th to 10th Most 
Recent Fault
Fault 
Message 
Displays the fifth to the tenth most recent faults.
After ten faults, data for the oldest fault is deleted. The most recent fault 
appears in U3-01, with the next most recent fault appearing in U3-02. The 
data is moved to the next monitor parameter each time a fault occurs.
No signal 
output 
available
–
U3-11 to
U3-14
(94H to
97H)
Cumulative 
Operation Time at 
1st to 4th Most 
Recent Fault
Elapsed 
Time 
Displays the cumulative operation time when the first to the fourth most 
recent faults occurred.
No signal 
output 
available
1 h
U3-15 to
U3-20
(80EH to
813H)
Cumulative 
Operation Time at 
5th to 10th Most 
Recent Fault
Elapsed 
Time 
Displays the cumulative operation time when the fifth to the tenth most 
recent faults occurred.
No signal 
output 
available
1 h
U4: Maintenance Monitors
U4-01
(4CH)
Cumulative 
Operation Time
Drv 
Elapsed 
Time
Displays the cumulative operation time of the regenerative unit. The value 
for the cumulative operation time counter can be reset in parameter o4-01. 
Use parameter o4-02 to determine if the operation time should start as 
soon as the power is switched on or only while the Run command is 
present. The maximum number displayed is 99999, after which the value 
is reset to 0.
No signal 
output 
available
1 h
No.
(Address
Hex)
Name
LCD
Display
Description
Analog
Output
Level
Unit