L: protection function – Yaskawa R1000 Series Power Regenerative Unit User Manual
Page 164

B.2 Parameter Tables
164
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
◆ L: Protection Function
Protection function parameters set momentary power loss processing, fault retries, and hardware protection.
H5-05
(0429)
Communication
Fault Detection
Selection
Serial Flt Dtct
0: Disabled
1: Enabled
0: Disabled
1: Enabled. If communication is lost for more than two seconds, a
CE fault will occur.
Default: 1
Range: 0, 1
H5-06
(042A)
Drive Transmit Wait
Time
Transmit WaitTIM
Set the wait time between receiving and sending data.
Default: 5 ms
Min.: 5 ms
Max.: 65 ms
H5-07
(042B)
RTS Control
Selection
RTS Control Sel
0: Disabled
1: Enabled
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.
Default: 1
Range: 0, 1
H5-09
(0435)
Communications
Fault Detection
Time
CE Detect Time
Sets the time required to detect a communications error.
Adjustment may be needed when networking several drives.
Default: 2.0 s
Min.: 0.0 s
Max.: 10.0 s
H5-11
(043C)
Communications
ENTER Function
Selection
Enter CommandSel
0: Enter Required
1: No EnterRequired
0: Drive requires an Enter command before accepting any
changes to parameter settings.
1: Parameter changes are activated immediately without the
Enter command (same as V7).
Default: 1
Range: 0, 1
No.
(Address
Hex)
Name
LCD Display
Description
Values
L2: Momentary Power Loss Ride-Thru
L2-01
(485H)
Momentary Power
Loss Operation
Selection
PwrL Selection
0: Disabled
1: Enbl with Timer
2: Enbl whl CPU act
0: Disabled. Regenerative unit trips on Uv1 fault when
power is lost.
1: Recover within the time set in L2-02. Uv1 will be
detected if power loss is longer than L2-02.
2: Recover as long as CPU has power. Uv1 is not detected.
Note: Even if L2-01 is set to 1 or 2, the regenerative unit
may detect a fault when momentary-power-loss occurs
during regeneration or during no load.
Default: 0
Min.: 0
Max.: 2
L2-02
(486H)
Momentary Power
Loss Ride-Thru
Time
PwrL Ridethru t
Sets the Power Loss Ride-Thru time. Enabled only when
L2-01 = 1 or 3.
Default:
Min.: 0.0 s
Max.: 25.5 s
L2-05
(489H)
Undervoltage
Detection Level
(Uv)
PUV Det Level
There is normally no need to change this parameter from
the default value.
200 V Class
Default: 190 V
Min.: 150 V
Max.: 210 V
400 V Class
Default: 380 V
Min.: 300 V
Max.: 420 V
L2-21
(4D5H)
AUv Detection
Level
AC UV Level
Sets the undervoltage detection level for power supply
voltage (AC) in volts.
200 V Class
Default: 150 V
Min.: 100 V
Max.: 200 V
400 V Class
Default: 300 V
Min.: 200 V
Max.: 400 V
L2-38
(11E3H)
Power Supply
Frequency
Excessive Deviation
Pre-alarm
pFDV DetectCount
Sets the number of times the regenerative unit detecting
PFDv (Power Supply Frequency Excessive Deviation
Pre-alarm). Disabled when set to 0.
Default: 4
Min.: 0
Max.: 30
No.
(Address
Hex)
Name
LCD Display
Description
Values
TOEP_C710656_08B_1_0.book 164 ページ 2015年2月5日 木曜日 午前10時7分