U1 - 12, U1 - 19 – Yaskawa R1000 Series Power Regenerative Unit User Manual
Page 169

B.2 Parameter Tables
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
169
B
U1-12
(4BH)
Drive Status
Int Ctl Sts 1
Verifies the regenerative unit operation status.
No signal
output
available
–
U1-13
(4EH)
Terminal A1 Input
Level
Term A1
Level
Displays the signal level to analog input terminal A1.
10 V: 100%
0.1%
U1-14
(4FH)
Terminal A2 Input
Level
Term A2
Level
Displays the signal level to analog input terminal A2.
10 V: 100%
0.1%
U1-15
(50H)
Terminal A3 Input
Level
Term A3
Level
Displays the signal level to analog input terminal A3.
10 V: 100%
0.1%
U1-18
(61H)
oPE Fault
Parameter
OPE Error
Code
Displays the parameter number that caused the oPE02 or oPE08 operation
error.
No signal
output
available
–
U1-19
(66H)
MEMOBUS/
Modbus Error
Code
Transmit
Err
Displays the contents of a MEMOBUS/Modbus error.
No signal
output
available
–
U1-25
(4DH)
Software Number
(Flash)
CPU 1 SW
Number
FLASH ID
No signal
output
available
–
U1-26
(5BH)
Software No.
(ROM)
CPU 2 SW
Number
ROM ID
No signal
output
available
–
U1-27
(7A8H)
Message ID
(OPR)
MessageID
(OPR)
Shows the message ID number for OPE.
No signal
output
available
–
U1-28
(7A9H)
Message ID
(INV)
MessageID
(INV)
Shows the message ID number for INV.
No signal
output
available
–
U1-52
(1081H)
DC Bus Voltage
Feedback
DC V
Feedback
Shows the DC bus voltage feedback value.
200 V Class
10 V: 400 V
400 V Class
10 V: 800 V
1 V
U1-54
(1083H)
Power Supply
Voltage
AC Voltage Shows the power supply voltage.
200 V Class
10 V: 400 V
400 V Class
10 V: F800 V
1 V
U1-55
(1084H)
Power Supply
Current
AC Current Shows the current on the power supply side.
10 V: Rated
Input Current
1 A
No.
(Address
Hex)
Name
LCD
Display
Description
Analog
Output
Level
Unit
U1 - 12=
0 0 0 0 0 0 0 0
Bit 0: During RUN
Bit 1: Reserved
Bit 2: Reserved
Bit 3: Fault reset signal input
Bit 4: Power supply established
(0: Not completed, 1: Completed)
Bit 5: Operation ready
Bit 6: Minor fault detected
Bit 7: Fault detected
YAI
U1 - 19=
0 0 0 0 0 0 0 0
CRC Error
Data Length Error
Not Used
Parity Error
Overrun Error
Framing Error
Timed Out
Not Used
1
1
0
1
1
1
1
0
TOEP_C710656_08B_1_0.book 169 ページ 2015年2月5日 木曜日 午前10時7分