Terminal configuration, Wire size and torque specifications, 9 control circuit wiring – Yaskawa R1000 Series Power Regenerative Unit User Manual
Page 60

3.9 Control Circuit Wiring
60
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
◆ Terminal Configuration
The control circuit terminals are arranged as shown in
.
Figure 3.20
Figure 3.23 Control Circuit Terminal Arrangement
■
Wire Size and Torque Specifications
Select appropriate wire type and gauges from
.
For simpler and more reliable wiring, use crimp ferrules on the wire ends. Refer to
for ferrule terminal types
and sizes.
Table 3.8 Wire Gauge and Torque Specifications
Terminal
Screw
Size
Tightening
Torque
Nxm
(lbxin.)
Bare Wire Terminal
Ferrule-Type Terminal
Wire Type
Recomm.
Gauge
mm
2
(AWG)
Applicable
Gauge
mm
2
(AWG)
Recomm.
Gauge
mm
2
(AWG)
Applicable
Gauge
mm
2
(AWG)
FM, AC, AM, SC, SP, SN, A1,
A2, A3, +V, -V, S1 to S8, MA,
MB, MC, M1 to M6
M3.5
0.8 to 1.0
(7.1 to 8.6)
0.75
(18)
0.5 to 2
(20 to 14)
–
–
Shielded wire,
etc.
E (G)
M3.5
0.8 to 1.0
(7.1 to 8.6)
1.25
(12)
0.5 to 2
(20 to 14)
IG, R+, R-, S+, S-
M2
0.22 to 0.25
(1.9 to 2.2)
0.75
(18)
Stranded wire:
0.25 to 1.0
(24 to 17)
Solid wire:
0.25 to 1.5
(24 to 16)
0.5
(20)
0.25 to 0.5
(24 to 20)
㪤㪘 㪤㪙 㪤㪚
㪤㪊 㪤㪋 㪤㪍
㪤㪈 㪤㪉 㪤㪌
㪛㪤㪄
㪠㪞 㪩㪂 㪩㪄 㪪㪂 㪪㪄
㪟㪚 㪟㪈 㪟㪉
㪛㪤㪂
㪜㩿㪞㪀
㪘㪊 㪝㪤 㪘㪤 㪘㪚 㪤㪧 㪩㪧 㪘㪚
㪘㪚 㪭㪄 㪘㪈 㪘㪉
㪭㪂
㪪㪈 㪪㪉 㪪㪊 㪪㪋 㪪㪌 㪪㪍 㪪㪎
㪪㪥 㪪㪚 㪪㪧
㪪㪏
㪤㪘 㪤㪙 㪤㪚
㪤㪊 㪤㪋 㪤㪍
㪤㪈 㪤㪉 㪤㪌
㪘㪊 㪝㪤 㪘㪤 㪘㪚 㪤㪧 㪩㪧 㪘㪚
㪘㪚 㪭㪄 㪘㪈 㪘㪉
㪭㪂
㪪㪈 㪪㪉 㪪㪊 㪪㪋 㪪㪌 㪪㪍 㪪㪎
㪪㪥 㪪㪚 㪪㪧
㪪㪏
㪛㪤㪄
㪠㪞 㪩㪂 㪩㪄 㪪㪂 㪪㪄
㪟㪚 㪟㪈 㪟㪉
㪛㪤㪂
㪜㩿㪞㪀
YAI
TOEP_C710656_08B_1_0.book 60 ページ 2015年2月5日 木曜日 午前10時7分