Alarm outputs for maintenance monitors, Related parameters – Yaskawa R1000 Series Power Regenerative Unit User Manual
Page 120

6.3 Periodic Maintenance
120
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
■
Alarm Outputs for Maintenance Monitors
An output can be set up to inform the user when a specific components has neared its expected performance life.
When one of multi-function relay output terminals has been assigned the maintenance monitor function (H2- = 2F),
the terminal will close when the cooling fan, DC bus capacitors, or DC bus pre-charge relay reach 90% of the expected
performance life. Additionally the digital operator will display an alarm like shown in
to indicate the specific
components that may need maintenance.
Table 6.5 Maintenance Alarms (H2-01 to H2-03 = 2F)
■
Related Parameters
NOTICE: Use parameters o4-03, o4-05, and o4-07 to reset a Maintenance Monitor to zero after replacing a specific component. If
these parameters are not reset after the corresponding parts have been replaced, the Maintenance Monitor function will continue to
count down the performance life from the value that was reached with the old part.
Table 6.6 Maintenance Setting Parameters
Digital Operator Alarm
Display
Function
Corrective Action
LT-1
The cooling fans, the DC bus capacitors, or the DC bus
charge circuit have reached 90% of their designated
life time
Replace the cooling fan.
LT-2
Contact a Yaskawa representative or the nearest
Yaskawa sales office on possible regenerative unit
replacement.
LT-3
Contact a Yaskawa representative or the nearest
Yaskawa sales office on possible regenerative unit
replacement.
No.
Name
Function
o4-03
<1> Parameter o4-03 is set in increments of 10 hours. For example, setting o4-03 to 30 set the operating time for cooling fan maintenance 300 hours
and the Cooling Fan Operation Time monitor (U4-03) will show 300 hours.
<2> The maintenance period depends on the operating environment of the regenerative unit.
Cooling Fan Operation Time
Setting
Sets the value of the fan operation time monitor U4-03 in units of 10 h.
o4-05
Capacitor Maintenance Setting
Sets the value of the Maintenance Monitor for the capacitors.
o4-07
DC Bus Pre-Charge Relay
Maintenance Setting
Sets the value of the Maintenance Monitor for the soft charge bypass relay.