6.4 Cooling Fans
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
129
Per
iodic Ins
pec
tion
&
Maint
ena
nc
e
6
Cooling Fan Wiring: 2A0073, 4A0105, 4A0150
1.
Position the protective tube so the fan connector sits in the center of the protective tube.
2.
Insert the connector for fan B2 and guide the lead wire for fan B2 so the cable hook holds it in place. Insert the
connector for fan B1.
Figure 6.17
Figure 6.17 Cooling Fan Wiring: 2A0073, 4A0105, 4A0150
3.
Double-check the relay connector to ensure it is properly connected.
Cooling Fan Wiring: 2A0105, 4A0210 to 4A0300
1.
Position the protective tube so the fan connector sits in the center of the protective tube.
2.
In the space between fans 1 and 2, place the fan connector for fan B2 in front of the fan connector for fan B1.
3.
Place the connector for fan B3 between fans B2 and B3.
Note: Model 2A0105 does not have the fan B3.
Figure 6.18
Figure 6.18 Cooling Fan Wiring: 2A0053 to 2A0105, 4A0053 to 4A0300
Protective tube