Using the contact outputs, Table 3.11, Set parameter – Yaskawa R1000 Series Power Regenerative Unit User Manual
Page 64: As shown in, Table 3.12, 10 control i/o connections

3.10 Control I/O Connections
64
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
Table 3.11 DIP Switch S1 Settings
Table 3.12 Parameter H3-09 Details
◆ Using the Contact Outputs
illustrates the use of multi-function relay outputs and the fault relay outputs.
Figure 3.26
Figure 3.29 Contact Outputs
Setting
Description
V (left position)
Voltage input (-10 to +10 V or 0 to 10 V)
I (right position)
Current input (4 to 20 mA or 0 to 20 mA): default setting
No.
Parameter Name
Description
Setting
Range
Default
Setting
H3-09
Terminal A2 signal level selection
Selects the signal level for terminal A2.
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3
2
<1> Minimum load: 5 Vdc, 10 mA
M
M
5
3
4
M
M
6
MA
M1
M2
MB
MC
Relay
SA
SA
Max
250 Vac
Relay
Relay
Relay
Max 250 Vac
Max 250 Vac
Controller
Multi-function relay output
<1>
250 Vac, max. 1 A
30 Vdc, max. 1 A
Fault relay output
<1>
250 Vac, max. 1 A
30 Vdc, max. 1 A
Through mode
Fault
Through mode
Through mode
Regenerative Unit
YAI