7.4 Standard Configuration Devices Wiring
142
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
◆ Terminal Functions
■
Power Coordinating Reactor
Table 7.3 Terminal Function (Power Coordinating Reactor)
■
Current Suppression Reactor
Table 7.4 Terminal Function (Current Suppression Reactor)
4A0105
U, V, W
50
50 to 150
2/0
2/0 to 300
50
50 to 150
M10
18.0 to 23.0
(159 to 204)
X, Y, Z
R, S, T
4A0150
U, V, W
100
100 to 150
250
250 to 300
95
95 to 240
M12
32.0 to 40.0
(283 to 354)
X, Y, Z
R, S, T
4A0210
U, V, W
80
×
2P
80 to 325
3/0
×
2P
3/0 to 600
95
×
2P
95 to 240
M12
32.0 to 40.0
(283 to 354)
X, Y, Z
R, S, T
4A0300
U, V, W
100
×
2P
100 to 325
250
×
2P
250 to 600
95
×
2P
95 to 240
M12
32.0 to 40.0
(283 to 354)
X, Y, Z
R, S, T
<1> Gauges listed here are for use in Japan.
<2> Gauges listed here are for use in the United States.
<3> Gauges listed here are for use in Europe and China.
Terminal
Function
U
Power Coordinating Reactor Inputs
These terminals are connected to the power supply.
V
W
X
Power Coordinating Reactor Outputs
These terminals are connected to the connected drive device input terminals and
input fuses.
Y
Z
Terminal
Function
X
Current Suppression Reactor Inputs
These terminals are connected to the input fuses.
Y
Z
R
Current Suppression Reactor Outputs
These terminals are connected to the regenerative unit.
S
T
Model
Terminals
For Asia
<1>
For U.S.A.
<2>
For Europe and China
<3>
Screw
Size
Tightening
Torque
Nxm
(lbxin.)
Recomm.
Gauge
mm
2
Applicable
Gauge
mm
2
Recomm.
Gauge
AWG, kcmil
Applicable
Gauge
AWG, kcmil
Recomm.
Gauge
mm
2
Applicable
Gauge
mm
2
TOEP_C710656_08B_1_0.book 142 ページ 2015年2月5日 木曜日 午前10時7分