B.3 Defaults by Unit Model

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

173

Par

ame

te

r Li

st

B

B.3 Defaults by Unit Model

The following tables show parameters and default settings that change with o2-04 (Unit Model Selection).

Table B.1 200 V Class Model Default Settings by Regenerative Unit Model Selection

Table B.2 400 V Class Model Default Settings by Regenerative Unit Model Selection

No.

Name

Unit

Default Settings

Model

– 2A03P5 2A0005 2A0007 2A0010 2A0014 2A0017 2A0020 2A0028 2A0035 2A0053 2A0073 2A0105

o2-04

Unit Model

Selection

Hex

68

6A

6B

6D

6E

6F

70

72

73

75

76

78

C7-14

Bias Voltage at
Operation Start

V

2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

C7-15

Voltage Hysteresis
Width at Operation
Start/Stop

V

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

L2-02

Momentary Power
Loss Ride-Thru
Time

s

1.0 1.0 1.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

L2-05

Undervoltage
Detection Level
(Uv)

V

190

190

190

190

190

190

190

190

190

190

190

190

L2-21

AUv Detection
Level

V

150

150

150

150

150

150

150

150

150

150

150

150

L8-02

Overheat Alarm
Level

°C

85

105

110

115

115

120

120

120

110

115

110

120

L8-66

Power Supply Fault
Detection Voltage
Level

%

50

50

50

50

50

50

50

50

50

50

50

50

L8-35

Installation Method
Selection

2

2

2

2

2

2

2

2

2

2

0

0

No.

Name

Unit

Default Settings

Model

4A03P5 4A0005 4A0007 4A0010 4A0014 4A0017 4A0020 4A0028

o2-04

Unit Model Selection

Hex

97

99

9A

9C

9D

9E

9F

A1

C7-14 Bias Voltage at Operation Start

V

4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0

C7-15

Voltage Hysteresis Width at Operation
Start/Stop

V

6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0

L2-02 Momentary Power Loss Ride-Thru Time

s

1.0 1.0 1.0 2.0 2.0 2.0 2.0 2.0

L2-05 Undervoltage Detection Level (Uv)

V

380

380

380

380

380

380

380

380

L2-21 AUv Detection Level

V

300

300

300

300

300

300

300

300

L8-02 Overheat Alarm Level

°C

80

85

100

95

110

105

115

110

L8-66

Power Supply Fault Detection Voltage
Level

%

50

50

50

50

50

50

50

50

L8-35 Installation Method Selection

2

2

2

2

2

2

2