Yaskawa R1000 Series Power Regenerative Unit User Manual
Page 158

B.2 Parameter Tables
158
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
F4-02
(392H)
Terminal V1
Monitor Gain
AO Ch1 Gain
Sets the gain for voltage output via terminal V1.
Default: 100.0%
Min.: -999.9%
Max.: 999.9%
F4-03
(393H)
Terminal V2
Monitor Selection
AO Ch2 Select
Sets the monitor signal for output from terminal V2. Set
this parameter to the last three digits of the desired
U- monitor. Some U parameters are available only
in certain control modes.
Default: 0
Min.: 000
Max.: 408
F4-04
(394H)
Terminal V2
Monitor Gain
AO Ch2 Gain
Sets the gain for voltage output via terminal V2.
Default: 50.0%
Min.: -999.9%
Max.: 999.9%
F4-05
(395H)
Terminal V1
Monitor Bias
AO Ch1 Bias
Sets the amount of bias added to the voltage output via
terminal V1.
Default: 0.0%
Min.: -999.9%
Max.: 999.9%
F4-06
(396H)
Terminal V2
Monitor Bias
AO Ch2 Bias
Sets the amount of bias added to the voltage output via
terminal V2.
Default: 0.0%
Min.: -999.9%
Max.: 999.9%
F4-07
(397H)
Terminal V1 Signal
Level
AO Opt Level Ch1
0: 0-10 VDC
1: -10 +10 VDC
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min.: 0
Max.: 1
F4-08
(398H)
Terminal V2 Signal
Level
AO Opt Level Ch2
0: 0-10 VDC
1: -10 +10 VDC
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min.: 0
Max.: 1
F5: Digital Output Card (DO-A3)
F5-01
(399H)
Terminal P1-PC
Output Selection
DO Ch1 Select
Sets the function for contact output terminals M1-M2,
M3-M4, and photocoupler output terminals P1 through P6.
Default: F
Min.: 0
Max.: 160
F5-02
(39AH)
Terminal P2-PC
Output Selection
DO Ch2 Select
Default: F
Min.: 0
Max.: 160
F5-03
(39BH)
Terminal P3-PC
Output Selection
DO Ch3 Select
Default: F
Min.: 0
Max.: 160
F5-04
(39CH)
Terminal P4-PC
Output Selection
DO Ch4 Select
Default: F
Min.: 0
Max.: 160
F5-05
(39DH)
Terminal P5-PC
Output Selection
DO Ch5 Select
Default: F
Min.: 0
Max.: 160
F5-06
(39EH)
Terminal P6-PC
Output Selection
DO Ch6 Select
Default: F
Min.: 0
Max.: 160
F5-07
(39FH)
Terminal M1-M2
Output Selection
DO Ch7 Select
Default: F
Min.: 0
Max.: 160
F5-08
(3A0H)
Terminal M3-M4
Output Selection
DO Ch8 Select
Default: F
Min.: 0
Max.: 160
F6: Communication Option Card
For details on a specific option card, refer to the instruction manual for the option card.
No.
(Address
Hex)
Name
LCD Display
Description
Values
TOEP_C710656_08B_1_0.book 158 ページ 2015年2月5日 木曜日 午前10時7分