B.2 Parameter Tables

166

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

o: Operator-Related Settings

The o parameters set up the digital operator displays.

L8-66

(670H)

Power Supply Fault
Detection Voltage
Level

Vpn Ripple Lvl

There is normally no need to change this parameter from
the default value. The main circuit DC voltage ripple is
monitored in a cycle of 200 ms. If the difference between
the maximum and minimum values of the ripple exceeds
the value that is set in L8-66 for the number of times that is
set in L8-67, a power supply fault is detected.

200 V Class

Default:

<2>

Min.: 1
Max.: 200

400 V Class

Default:

<2>

Min.: 1
Max.: 200

L8-67

(671H)

Number of Times of
Power Supply Fault
for Detection

Vpn Ripple Cnt

Default: 5
Min.: 1
Max.: 10

L8-69

(673H)

Input Phase Loss
Protection Selection
3

AC Phase Imb Det
0: Disabled
1: Enabled

Sets whether to enable or disable the protective function
for the regenerative unit when there is an input phase loss.
0: Disabled
1: Enabled (Detect input phase loss and power supply
imbalance.)

Default: 1
Min.: 0
Max.: 1

<2> Default setting is dependent on parameter o2-04, Unit Model Selection.

No.

(Address

Hex)

Name

LCD Display

Description

Values

o1: Digital Operator Display Selection

o1-01

(500H)

Drive Mode Monitor
Selection

User Monitor Sel

When the power supply is turned on, the operator will
display the following in order: DC Bus Voltage Feedback
Reference, Input Voltage, Power Supply Current, Power
Supply Power, Power Supply Frequency, and U1-††.
The o1-01 parameter sets the item to display instead of the
output voltage.
The o1-02 parameter sets the item to display at power up.

Default: 158
(Monitor U1-58)
Min.: 110
Max.: 914

o1-02

(501H)

User Monitor
Selection after
Power Up

Power-On Monitor
1: Frequency Ref
2: FWD/REV
3: Output Freq
4: Output Current
5: User Monitor

Selects the information displayed on the digital operator
when the power is turned on.
1: Output Voltage Feedback
2: Input Voltage
3: Power Supply Current
4: Power Supply Power
5: User monitor item set in o1-01

Default: 1
Min.: 1
Max.: 5

o1-05

(504H)

<7>

LCD Contrast
Control

LCD Contrast

Sets the brightness of the LCD operator.

Default: 3
Min.: 0
Max.: 5

o2: Digital Operator Keypad Functions

o2-01

(505H)

LO/RE Key
Function Selection

LO/RE Key

0: Disabled
1: Enabled. LO/RE key switches between LOCAL and
REMOTE operation.

Default: 1
Min.: 0
Max.: 1

o2-02

(506H)

STOP Key Function
Selection

Oper STOP Key
0: Disabled
1: Enabled

0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.

Default: 1
Min.: 0
Max.: 1

No.

(Address

Hex)

Name

LCD Display

Description

Values

TOEP_C710656_08B_1_0.book 166 ページ 2015年2月5日 木曜日 午前10時7分