A.4 Derating Data

The regenerative unit can be operated above the rated temperature, altitude, and default carrier frequency by derating the
unit capacity.

Temperature Derating

To ensure the maximum performance life, the regenerative unit output current must be derated as shown in

Figure A.1

when the regenerative unit is installed in areas with high ambient temperature or if regenerative units are mounted
side-by-side in a cabinet. In order to ensure reliable overload protection, set parameters L8-35 according to the
installation conditions.

Parameter Settings

If the ambient temperature is higher than the rating or if regenerative units are installed side by side in the control panel,
you must set the L8-12 and L8-35 parameters according to the installation conditions. Derate the output current according
to

Figure A.1

Setting 0: IP00 Open Type Enclosure

Regenerative unit operation between -10

°C and +50°C allows 100% continuous current without derating.

Setting 1: Side-by-Side Mounting

Regenerative unit operation between -10

°C and +30°C allows 100% continuous current without derating. Operation

between +30

°C and +50°C requires output current derating.

Setting 2: IP20/NEMA Type 1 Enclosure

Regenerative unit operation between -10

°C and +40°C allows 100% continuous current without derating. Operation

between +40

°C and +50°C requires output current derating.

Setting 3: External Heatsink Installation

Regenerative unit operation between -10

°C and +40°C allows 100% continuous current without derating. Operation

between +40

°C and +50°C requires output current derating.

Figure A.1

Figure A.1 Ambient Temperature and Installation Method Derating

No.

Name

Description

Setting Value

Default Setting

L8-12

Ambient Temperature
Setting

Adjust the Overload (oL2) protection level when the
regenerative unit is installed in an environment that
exceeds its ambient temperature rating.

-10 to +50

+40

°C

L8-35

Installation Method
Selection

0: IP00 Open Type Enclosure
1: Side-by-Side Mounting
2: IP20/NEMA Type 1 Enclosure
3: External Heatsink Installation

0 to 3

Default setting is

determined by o2-04

(Unit Model

Selection).

100

85

70

55

0

L8-35=2: IP20/NEMA Type 1 Enclosure
L8-35=3: External Heatsink Installation

L8-35=0: IP00 Open Type Enclosure

30

-10

40

50

L8-12
(Ambient temp: °C)

L8-35=1: Side-by-Side Mounting