Yaskawa R1000 Series Power Regenerative Unit User Manual
Page 192

C.9 MEMOBUS/Modbus Data Table
192
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
00C0H
Fault Contents 3
bit 0
DC Fuse Blowout (PUF)
bit 1
Undervoltage (Uv1)
bit 2
Control Power Supply Undervoltage (Uv2)
bit 3
Soft Charge Circuit Fault (Uv3)
bit 4
IGBT Short Circuit (SC)
bit 5
Reserved
bit 6
Overcurrent (oC)
bit 7
Overvoltage (ov)
bit 8
Heatsink Overheat (oH)
bit 9
Overheat 1 (oH1)
bit A
Reserved
bit B
Overload (oL2)
bit C - bit F
Reserved
00C1H
Fault Contents 4
bit 0
External Fault at input terminal S3 (EF3)
bit 1
External Fault at input terminal S4 (EF4)
bit 2
External Fault at input terminal S5 (EF5)
bit 3
External Fault at input terminal S6 (EF6)
bit 4
External Fault at input terminal S7 (EF7)
bit 5
External Fault at input terminal S8 (EF8)
bit 6
Cooling Fan Error (Fan)
bit 7 - bit C
Reserved
bit D
Digital Operator Connection Fault (oPr)
bit E
EEPROM Write Error (Err)
bit F
Reserved
00C2H
Fault Contents 5
bit 0
MEMOBUS/Modbus Communication Error (CE)
bit 1
Option Communication Error (bUS)
bit 2 - bit 5
Reserved
bit 6
Option External Fault (EF0)
bit 7 - bit E
Reserved
bit F
Hardware Fault (includes oF)
00C3H
Fault Contents 6
bit 0 - bit 7
Reserved
bit 8
MECHATROLINK Watchdog Timer Error (E5)
bit 9 - bit F
Reserved
00C4H
Fault Contents 7
bit 0
Reserved
bit 1
External Fault 1, input terminal S1 (EF1)
bit 2
External Fault 2, input terminal S2 (EF2)
bit 3 - bit 4
Reserved
bit 5
Current Offset Fault (CoF)
bit 6 - bit F
Reserved
00C5H
Fault Contents 8
bit 0
Reserved
bit 1
Node Setup Fault (nSE)
bit 2 - bit F
Reserved
Register No.
Contents
TOEP_C710656_08B_1_0.book 192 ページ 2015年2月5日 木曜日 午前10時7分