C.9 MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
193
MEMO
BUS/Mod
bus
Co
mmunica
tion
s
C
00C6H
Fault Contents 9
bit 0 - bit 4
Reserved
bit 5
Power Supply Undervoltage (AUv)
bit 6
Power Supply Overvoltage (Aov)
bit 7
Power Supply Frequency Fault (Fdv)
bit 8
Power Phase Rotation Variation (SrC)
bit 9
Input Power Supply Fault (PF2)
bit A
Input Phase Loss 3 (PF3)
bit B - E
Reserved
bit F
AC Fuse Blowout (FUA)
00C7H
Reserved
00C8H
Alarm Contents 2
bit 0
Undervoltage (Uv)
bit 1
Overvoltage (ov)
bit 2
Heatsink Overheat (oH)
bit 3
Overheat 2 (oH2)
bit 4 - bit 6
Reserved
bit 7
Baseblock (bb)
bit 8
External Fault 3, input terminal S3 (EF3)
bit 9
External Fault 4, input terminal S4 (EF4)
bit A
External Fault 5, input terminal S5 (EF5)
bit B
External Fault 6, input terminal S6 (EF6)
bit C
External Fault 7, input terminal S7 (EF7)
bit D
External Fault 8, input terminal S8 (EF8)
bit E
Cooling Fan Error (Fan)
bit F
Reserved
00C9H
Alarm Contents 3
bit 0 - bit 1
Reserved
bit 2
Digital Operator Connection Fault (oPr)
bit 3
MEMOBUS/Modbus Communication Error (CE)
bit 4
Option Communication Error (bUS)
bit 5
Serial Communication Transmission Error (CALL)
bit 6
Reserved
bit 7
Overload (oL2)
bit 8
Reserved
bit 9
Option Card External fault (EF0)
bit A - bit B
Reserved
bit C
Serial Communication Transmission Error (CALL)
bit D - bit E
Reserved
bit F
MEMOBUS/Modbus Test Mode Fault (SE)
00CAH
Reserved
Register No.
Contents