C.9 MEMOBUS/Modbus Data Table

YASKAWA ELECTRIC TOEP C710656 08B YASKAWA Power Regenerative Unit - R1000 Instruction Manual

193

MEMO

BUS/Mod

bus

Co

mmunica

tion

s

C

00C6H

Fault Contents 9
bit 0 - bit 4

Reserved

bit 5

Power Supply Undervoltage (AUv)

bit 6

Power Supply Overvoltage (Aov)

bit 7

Power Supply Frequency Fault (Fdv)

bit 8

Power Phase Rotation Variation (SrC)

bit 9

Input Power Supply Fault (PF2)

bit A

Input Phase Loss 3 (PF3)

bit B - E

Reserved

bit F

AC Fuse Blowout (FUA)

00C7H

Reserved

00C8H

Alarm Contents 2
bit 0

Undervoltage (Uv)

bit 1

Overvoltage (ov)

bit 2

Heatsink Overheat (oH)

bit 3

Overheat 2 (oH2)

bit 4 - bit 6

Reserved

bit 7

Baseblock (bb)

bit 8

External Fault 3, input terminal S3 (EF3)

bit 9

External Fault 4, input terminal S4 (EF4)

bit A

External Fault 5, input terminal S5 (EF5)

bit B

External Fault 6, input terminal S6 (EF6)

bit C

External Fault 7, input terminal S7 (EF7)

bit D

External Fault 8, input terminal S8 (EF8)

bit E

Cooling Fan Error (Fan)

bit F

Reserved

00C9H

Alarm Contents 3
bit 0 - bit 1

Reserved

bit 2

Digital Operator Connection Fault (oPr)

bit 3

MEMOBUS/Modbus Communication Error (CE)

bit 4

Option Communication Error (bUS)

bit 5

Serial Communication Transmission Error (CALL)

bit 6

Reserved

bit 7

Overload (oL2)

bit 8

Reserved

bit 9

Option Card External fault (EF0)

bit A - bit B

Reserved

bit C

Serial Communication Transmission Error (CALL)

bit D - bit E

Reserved

bit F

MEMOBUS/Modbus Test Mode Fault (SE)

00CAH

Reserved

Register No.

Contents