beautypg.com

5 technical data, 1 specifications – SMA MLX Series User Manual

Page 32

background image

5 Technical Data

5.1 Specifications

Parameter

MLX 60

AC

Rated apparent power

1)

60 kVA

Rated active power

2)

60 kW

Reactive power range

1)

0–36 kVAr

Rated grid voltage (voltage range)

3P + PE (delta or WYE) / 400-480 V (+/- 10%)

Grounding schemes supported

TT, TN

Rated current AC

3 x 87 A

Max. current AC

3 x 87 A

AC current distortion (THD at nominal output power)

< 5%

Power factor default

> 0.99 at rated power

Power factor - regulated

0.8 over-excited, 0.8 under-excited

Stand-by power consumption (comm. only)

3 W

Rated grid frequency (frequency range)

50/60 Hz (+/- 10%)

DC

Input voltage range

565–1000 V @ 400 V

ac

680–1000 V @ 480 V

ac

Rated voltage DC

630 V @ 400 V

ac

710 V @ 480 V

ac

MPPT voltage range - rated power

570–800 V @ 400 V

ac

685–800 V @ 480 V

ac

Max. voltage DC

1000 V

Min. on grid power

100 W

Max. MPPT current DC

110 A

Max. short-circuit current DC

150 A

MPP tracker / Input per MPPT

1 / 1 (external string combining)

Efficiency

Max. efficiency

98.6% (preliminary value)

EU / CEC efficiency at V

dc,r

98.0% / 98.0% (preliminary value)

MPPT efficiency static

99.9% (preliminary value)

Enclosure

Dimensions (H x W x D)

740 × 570 × 300 mm (29 × 22.5 × 12 in)

Weight

75 kg (165 lbs)

3)

Acoustic noise level

55 dB(A) (preliminary value)

Table 5.1 Specifications

1)

At rated grid voltage.

2)

At rated grid voltage, Cos(phi)=1.

3)

Depending on installed options.

Technical Data

L00410644-01_2q / Rev. date: 2014-06-02

31

5

5