beautypg.com

2 turn pv load switch on, 1 initial setup via lcs tool, 3 start-up – SMA MLX Series User Manual

Page 22: Warning, Notice

background image

Illustration 3.1 Overview of Display Buttons and Functionality

Key

Function

F1

Adjust contrast level of display. Use

arrow up/down button while holding

down the F1 button.

F2

Not in use

F3

F4

Home

Return to main screen

OK

Not in use

Arrow Up

A step up

Arrow Down

A step down

Arrow Right

Toggles screen right

Arrow Left

Toggles screen left

Back

Return to main screen

On - Green LED

Alarm - Red LED

Table 3.2 Overview of Display Buttons and Functionality

The screen structure is divided into 3 sections:

1.

Main screen. Current and daily production. This
section contains:

Actual power output (kW)

Energy counter current day (kWh)

Total energy counter (kWh)

Current date

Current time

Operation mode (

#)

2.

Inverter information. This section contains:

Inverter type

Inverter name

Serial no.

IP address

Inverter Manager MAC address

Inverter software version

3.

Actual values. This section contains:

PV voltage and current

Phase-to-phase voltages

Phase currents

Grid frequency

3.2.1 Initial Setup via LCS Tool

The LCS Tool makes it possible to chose from a list of
predefined settings for different grids. All grid-specific
limits must be configured using the LCS Tool.
After installation, check all cables and close the inverter.
Turn on AC power.

WARNING

Correct selection of grid code is essential to comply with
local and national standards.

3.2.2 Turn PV Load Switch On

Illustration 3.2 PV Load Switch

Turn PV load switch on, either via inverter or string
combiner.

3.2.3 Start-up

The inverter starts automatically if sufficient solar
irradiation is available. The start-up takes a few minutes.
During this period, the inverter performs a self-test
procedure.

NOTICE

The inverter is protected against reversed polarity. The
inverter does not generate power until any reversed
polarity is corrected.

Initial Setup and Start

L00410644-01_2q / Rev. date: 2014-06-02

21

3

3