background image

Illustration 3.8 LCS Tool - Verification of Country and Grid Code

8.

The system now applies the selected grid code to
the Inverter Manager and the discovered
inverters. Any inverter added at a later stage
automatically inherits the same grid code. Only 1
grid code per Inverter Manager is possible.

NOTICE

It is essential to choose the correct grid code. The grid
code cannot be changed afterwards without contacting
SMA.

9.

A green square identifies the commissioned
inverters. However, the inverters do not connect
to grid before a ‘Start’ command is issued from
the bar below the top menu. See Illustration 3.9.

Initial Setup and Start

L00410644-01_2q / Rev. date: 2014-06-02

25

3

3