Element continuous/3-position controller, Controller menu – Flowserve SPECTORcontrol User Manual
Page 59
59
– continued –
3-element 3-position controller setup
- contin ued -
14. The green input field
Offset
shows the current value. To enter or change a value click
in the input field.
15. The adjusted value appears in the input mask. Use the on-screen keyboard to over-
write or modify the value.
16. The green input fields
Min/Max limit
show the current limit values. To enter or
change a value click in the input field.
17. The adjusted value appears in the input mask. Use the on-screen keyboard to over-
write or modify the value.
18. The green input fields
Min. pulse
and
Valve run time
show the current values. To
enter or change a value click in the input field.
19. The adjusted value appears in the input mask. Use the on-screen keyboard to over-
write or modify the value.
3-element continuous/3-position controller
1.
Press button
Parameterised as
in the menu
3-element controller
.
2.
The menu is protected by password. Press
button
and enter your password.
3.
The values of the steam flowrate and the
water flowrate are highlighted in yellow.
Below that the current level, the status in-
dicator
Enabled/Disabled
and the adjust-
ed controller are shown. Next to these
values the setpoint and the current control-
ler setting are indicated.
4.
To change the internal setpoint click in
the green input field.
Note
The MIN and MAX limit values specify the admissible manipulated variable
range of the controller.
Controlled actual value = Level - (steam flowrate - water flowrate) x rating
if steam flowrate – water flowrate > 0.
If the steam or water flowrate signal is faulty, the controller will only use the
actual value of the level.
3-element
3-pos. controller
Logo
Water flowr.
Int. setpoint
Position
Steam flowr.
Level
Disabled
NC
0.0
0.00
0.00
0.0
0.0
0.00
0
0