Commissioning

Fig. 145: Enabling the axis in the NC

• If you don’t use the TwinCAT NC.

In this case you must run through the State Machine manually. Set the variable 0 x 7010:01 [

}

 186]

Enable to 1 (true), Fig. "Enabling the axis manually".

Fig. 146: Enabling the axis manually

• A defined position can be entered via the cyclic variable STM Position (Fig. "Entering the position").

The position is specified in increments and depends on the selected feedback (index 8012:0A [

}

 181]).

For an AS10xx motor with internal counter, 12,800 (64-fold microstepping * 200 full steps of the
AS10xx motor) corresponds to one full turn. With an external encoder the value depends on the
encoder. For an AS10xx motor encoder with 1024 INC/revolution, 4,096 (1024 INC/rev * 4-fold
evaluation) corresponds to one full turn.