Adding dynamic network variables – Echelon FTXL User Manual

Page 235

background image

FTXL User’s Guide

223

6. In the Select Network Variable Type dialog, expand

C:\LonWorks\Types\STANDARD.FMT and select either SNVT_volt or
SNVT_volt_mil. Click OK to change the type and close the Select

Network Variable Type dialog.


Important: You can only change the type for a network variable if it is

not bound to the network. LonMaker implicitly binds network variables
when you enable monitoring from the LonMaker drawing (from the

drawing itself or from any connections to the functional blocks) or the

LonMaker Browser window. Thus, you must disable monitoring for both
the nviVolt and nvoVoltFb network variables.

To verify that the type changed successfully:

1. Within the LonMaker Browser window, select the row for the nviVolt

network variable.

2. Right-click the nviVolt network variable and select Properties to open the

Network Variable Properties dialog.

3. On the Description page of the Network Variable Properties dialog, the

Type name field displays the current type for the network variable. The

current type should be either SNVT_volt or SNVT_volt_mil.

The valid range for the value of the nviVolt and nvoVoltFb network variables

depends on its current type:

• For nviVolt as SNVT_volt: ± 1.6 V
• For nvoVoltFb as SNVT_volt: ± 3.2 V
• For nviVolt as SNVT_volt_mil: -1638.4 mV to +1638.3 mV
• For nviVolt as SNVT_volt_mil: -3276.8 mV to +3276.6 mV

Important: Be sure to change the type to either SNVT_volt or SNVT_volt_mil,

not to SNVT_vol, SNVT_vol_mil, or any other type. If you change the type to an

invalid type, the dynamic interface example application rejects the change and
disables the NodeObject and VoltAmplifier functional blocks. In this case, you

must re-enable the functional blocks:

1. Change the type for either the nviVolt or nvoVoltFb network variable to a

valid type, SNVT_volt or SNVT_volt_mil.

2. Within the LonMaker drawing, right-click the NodeObject functional

block and select Manage to open the LonMaker Device Manager dialog.

3. From the Functional Blocks tab of the LonMaker Device Manager dialog,

click Enable to re-enable the functional block. Click Test to verify that
the output for the functional block displays “Diabled: 0”, which signifies

that the functional block is not disabled.

Adding Dynamic Network Variables

To add a set of dynamic network variables to the FTXL device to demonstrate a
logical circuit as described in

The Dynamic Interface Example Application

on

page 202:

1. Open the LonMaker drawing for the FTXL device.

2. Ensure that the FTXL device is properly configured and commissioned.