Running the Simple Example

To verify that the application runs as expected, connect the FTXL Transceiver

Board to a network management tool, such as the LonMaker tool. From the tool,
modify the value for the nviVolt network variable and confirm that the value for

the nvoVoltFb network variable is double that value:

1. Open the LonMaker drawing for the FTXL device.

2. Ensure that the FTXL device is properly configured, commissioned, and

online.

3. Right-click the FTXL device on the LonMaker drawing and select Browse

to open the LonMaker Browser window.

4. Within the LonMaker Browser window, select the row for the nviVolt

network variable.

5. Enter a value for the network variable in the Value field at the top of the

window. Click the Set value button to set the network variable’s value.

6. Select the row for the nvoVoltFb network variable, and click the Get

value button to see its current value. That value should be twice the

nviVolt value.

Running the Dynamic Interface Example

To verify that the application runs as expected, connect the FTXL Transceiver

Board to a network management tool, such as the LonMaker Integration tool.

From the tool, modify the value for the nviVolt network variable and confirm that
the value for the nvoVoltFb network variable is double that value, as described

for the simple example.
You can also change the type for the nviVolt or nvoVoltFb network variables, or
add dynamic variables for the logical circuits described in

The Dynamic Interface

Example Application

on page 202.

Changing Network Variable Types

To change the type of the two network variables that are defined for the

VoltAmplifier functional block:

1. Open the LonMaker drawing for the FTXL device.

2. Ensure that the FTXL device is properly configured, commissioned, and

online.

3. Right-click the FTXL device on the LonMaker drawing and select Browse

to open the LonMaker Browser window.

4. Select the row for either the nviVolt or nvoVoltFb network variable. Be

sure

not

to select the row for the corresponding configuration property

(displayed in green, with the value SCPTnvType in the Config Prop

column).

5. Right-click the nviVolt or nvoVoltFb network variable and select Change

Type to open the Select Network Variable Type dialog.