Hydraulic System Problems

Delta Computer Systems, Inc. 360/254-8688

71

If the speeds show:

Your valve is probably curvilinear. Replace the valve with a linear one or increase the proportional gain and
tune the system for high-speed stability; expect poor control at low speed and when stopped.

If the speeds show:

You may have too much hose between the valve and the cylinder. Reduce the amount of hose or add
differential gain (usually less than 5).