Jogging the axis, Saving parameters and profiles – Delta MMC120 User Manual
Page 26
Startup
MMC120 Linear Motion Control Module
26
Delta Computer Systems, Inc. 360/254-8688
increased. If the FOLLOWING ERROR occurs on an extend move, increase the EXTEND FEED
FORWARD; it the error occurs on a retract move, increase the RETRACT REED FORWARD. If this doesn't
solve the problem, the ACCELERATION and DECELERATION ramps are too steep for the response of the
system. Their values can be reduced, or the ACCEL FEED FORWARD and DECEL FEED FORWARD
terms can be increased. After the problem which caused the error has been corrected, keep moving the axis
back and forth with increasing speed until you reach the desired speed. Should the system seem a little sloppy,
try decreasing the MAXIMUM ERROR and adjusting the PROPORTIONAL GAIN until the axis can be
moved without getting an error. Remember: the parameters are not updated in the MMC120 until the 'P'
command is issued.
Jogging The Axis
You can jog the axis by setting the COMMAND VALUE to the EXTEND LIMIT or RETRACT LIMIT and
using the 'G' and 'H' commands repeatedly. This causes the Motion Control Module to GO and HALT.
Saving Parameters and Profiles
After the system is set up and tuned using DCS120, you need to store the parameter and profile values in the
Programmable Controller. This is done using Command Types A and B. Only the parameters for the axes
used need to be saved, and only the profiles used need to be saved.