Chapter 5 Parameters|VFD-S Series

5-42

Revision August 2006, SE08, SW V2.61

Frequency

Master Frequency

Acceleration
inhibit

Acceleration
inhibit

Actual operation frequency

Deceleration
inhibit

Deceleration
inhibit

Time

Mx-GND

Operation
command

ON

ON

ON

ON

ON

OFF


d12 First or Second Acceleration/Deceleration Time Selection:

Parameter value d12 programs a Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3

(Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) to control selection of First or Second

Acceleration/deceleration time. (Refer to Pr.1-09 to Pr.1-12.)

GND

Mx "Close": 2nd Acceleration/Deceleraion

Mx set d12

"Open": 1st Acceleration/Deceleration

Frequency

Master
Frequency

Pr.
1-09

1st
Acceleration/
Deceleration

2nd
Acceleration/
Deceleration

1st
Acceleration

Pr.
1-10

Pr.
1-12

Pr.
1-12

2nd
Deceleration

Time

Mx-GND

operation
command

ON

ON

ON

ON

ON

OFF

Pr.
1-11

Pr.
1-09

d13, d14 External Base Block:

Parameter values d13, d14 program Multi-Function Input Terminals: M1 (Pr.4-04), M2 (Pr.4-05), M3

(Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) for external Base Block control. Value d13 is for normally

open (N.O.) input, and value d14 is for a normally closed (N.C.) input.