Chapter 5 Parameters|VFD-S Series

5-32

Revision August 2006, SE08, SW V2.61

3-02

Desired Frequency Attained

Unit: 0.1

Settings

d1.0 to d400 Hz

Factory Setting: d1.0

If a multi-function output terminal is set to function as Desired Frequency Attained (Pr.3-05 or

3-06=d9), then the output will be activated when the programmed frequency is attained.

Desired Freq.

Detection
range

-2Hz

Detection range

+

-

4Hz

Detection range

+

-

2Hz

Time

Freq.

Max. Output
Freq.

Pr.3-02

ON

ON

OFF

OFF

OFF

OFF

Preset Freq.
Attained
indication
Pr.3-05 to 3-06

Desired Freq.
Attained
Indication
Pr.3-05 to 3-06

Desired Freq. Attained & Preset Freq. Attained

3-03

Terminal Count Value

Unit: 1

Settings

d0 to d999

Factory Setting: d0

The parameter determines the upper limit value of the internal counter. The internal counter

can be triggered by the external terminal (Pr.4-4 to Pr.4-8, d19). Upon completion of counting,

the specified output terminal will be activated. (Pr.3-05, Pr.3-06, d14).

3-04

Preliminary Count Value

Unit: 1

Settings

d0 to d999

Factory Setting: d0

When the counter value is counted up from “1” to the setting value of this parameter, the

corresponding multi-function output terminal which set to d15 as Preliminary Counter Value

Attained will be closed. The application can be that closing the multi-function output terminal

makes the AC drive operate at low speed until stop before the counting value is going to be

attained.

The timing diagram is shown below: