Chapter 7 Troubleshooting |VFD-S Series

Revision August 2006, SE08, SW V2.61

7-3

7.4 Low Voltage (Lv)

Low voltage

Is input power correct? Or power cut,
including momentary power loss

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

No

Restart after reset

Check if there is any malfunction
component in
power supply circuit

or disconnection

Change defective component
and check connection

Check if voltage is
within specification

Make necessary corrections,
such as change power supply
system for requirement

Check if there is heavy load
with high start current in the
same power system

Check if Lv occurs when
breaker and magnetic
contactor is ON

Suitable
transformer

power

capacity

Check if voltage between +1/+2
and - is greater than
200VDC (for 230V models)
400VDC (for 460V models)
517VDC (for 575V models)

Maybe AC motor drive has malfunction.
Please contact DELTA.

Control circuit has malfunction or
misoperation due to noise. Please
contact DELTA.

Yes

Using the different power
supply for this drive and
heavy load system