Chapter 5 Parameters|VFD-S Series

Revision August 2006, SE08, SW V2.61

5-41

GND

D7 Multi-step 1

D8 Multi-step 2

D9 Multi-step 3

Mx "Close": Operation available

Mx "Close": Operation available

Mx "Close": Operation available

These three inputs select the multi-step speeds defined by Pr.5-00 to Pr.5-06 as shown in the

following diagram. Pr.5-07 to Pr.5-16 can also control output speed by programming the AC drive’s

internal PLC function.

Freq.

Step 1

Step 2

Step 3

Step 4

Step 5

Step 6

Step 7

Time

OFF

ON

ON

ON ON

ON

ON

ON ON

ON ON ON ON

ON

Operation
Command

Mx3-GND

Mx2-GND

Mx1-GND

Pr.5-00

Pr.5-01

Pr.5-02

Pr.5-03

Pr.5-04

Pr.5-05

Pr.5-06

Master Freq.

d10 Jog Operation Control:

Parameter value d10 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.4-

06), M4 (Pr.4-07) or M5 (Pr.4-08) for Jog control.

GND

Mx "Close": Operation available

d10 jog operation
command

NOTE

Jog operation programmed by d10 can only be initiated while the motor is stopped. (Refer to Pr.1-13,

Pr.1-14.)

d11 Acceleration/Deceleration Speed Inhibit:

Parameter value d11 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.4-

06), M4 (Pr.4-07) or M5 (Pr.4-08) for Acceleration/deceleration Inhibit. When the command is

received, acceleration and deceleration is stopped and the AC drive maintains a constant speed.