Chapter 2 Installation and Wiring|VFD-S Series

2-26

Revision August 2006, SE08, SW V2.61

Terminal

Symbol

Terminal Function

Factory Settings (NPN mode)

ON: Connect to GND

AVI

Analog voltage Input
(AVI/ACI)

0~+10V/4-20mA corresponds to 0-max.

operation frequency (Pr.01-00)


PID feedback signal
AVI input impedance: 100kohm
ACI input impedance: 250kohm

GND

AVI

+10V

Internal Circuit

AVI circuit

AVI

J1

ACI

GND

ACI

Internal Circuit

ACI circuit

AVI

J1

ACI

Control signal wiring size: 18 AWG (0.75 mm

2

) with shielded wire.

Analog input terminals (AVI, GND)

Analog input signals are easily affected by external noise. Use shielded wiring and keep

it as short as possible (<20m) with proper grounding. If the noise is inductive, connecting

the shield to terminal GND can bring improvement.

If the analog input signals are affected by noise from the AC motor drive, please connect

a capacitor (0.1

μ

F and above) and ferrite core as indicated in the following diagrams:

C

AVI

GND

ferrite core

wind each wires 3 times or more around the core

Digital inputs (M0~M5, GND)

When using contacts or switches to control the digital inputs, please use high quality

components to avoid contact bounce.