beautypg.com

2 ground fault, 3 over voltage (ov), 2 ground fault -2 – Delta Electronics AC Motor Drive VFD007S23A User Manual

Page 139: 3 over voltage (ov) -2

background image

Chapter 7 Troubleshooting |VFD-S Series

7-2

Revision August 2006, SE08, SW V2.61

7.2 Ground Fault

GFF

Ground fault

No

Yes

Is output circuit(cable or
motor) of AC motor drive
grounded?

Remove ground fault

Maybe AC motor drive has
malfunction or misoperation
due to noise. Please
contact DELTA.

7.3 Over Voltage (OV)

Over voltage

Yes

No

Yes

No

No

No

Is voltage within
specification

Reduce voltage to
be within spec.

Has over-voltage occurred without load

Maybe AC motor drive
has malfunction or
misoperation due to
noise. Please contact
with DELTA.

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

When OV occurs, check if the
voltage of DC BUS is greater
than protection value

Dose OV occur when
sudden acceleration
stops

Increase
deceleration
time

Increase setting time

Increase
acceleration
time

Reduce moment
of inertia

Reduce moment of load inertia

Use braking unit or DC braking

Need to check control method. Please contact DELTA.

Need to consider using
braking unit or
DC braking