Chapter 5 Parameters|VFD-S Series

Revision August 2006, SE08, SW V2.61

5-5

Pr. Explanation

Settings

Factory

Setting

NOTE

3-00

Analog Output Signal

d0: analog frequency meter
d1: analog current meter

d0

3-01 Analog Output Gain

d1 to d200%

d100

3-02

Desired Frequency Attained

d1.0 to d400 Hz

d1.0

3-03

Terminal Count Value

d0 to d999

d0

3-04

Preliminary Count Value

d0 to d999

d0

3-05

Multi-Function Output Terminal 1
(Photocoupler Output)

d0: No Function

d1

3-06

Multi-Function Output Terminal 2
(Relay Output)

d1: AC Drive Operational
d2: Master Frequency Attained
d3: Zero Speed
d4: Over Torque Detection
d5: Base-Block (B.B.) Indication
d6: Low-Voltage Indication
d7: Operation Mode Indication
d8: Fault Indication
d9: Desired Frequency Attained
d10: PLC Program Running
d11: PLC Program Step Completed
d12: PLC Program Completed
d13: PLC Program Operation

Paused

d14: Terminal Count Value Attained
d15: Preliminary Count Value

Attained

d16: AC Motor Drive Ready
d17: FWD command Indication
d18: REV command Indication

d8

Group 4 Input Function Parameters

Pr. Explanation

Settings

Factory

Setting

NOTE

4-00 Potentiometer Bias Frequency

d 0.0 to d 100.0%

d0.0

4-01

Potentiometer Bias
Polarity

d0: Positive Bias
d1: Negative Bias

d0

4-02

Potentiometer
Frequency Gain

d1 to d200 %

d100

4-03

Potentiometer Reverse
Motion Enable

d0: Forward Motion Only
d1: Reverse Motion enabled

d0

4-04

Multi-Function Input Terminal 1 (M0,
M1)

d0: No Function
d1: FWD/STOP, REV/STOP
d2: FWD/REV, RUN/STOP
d3: 3-wire Operation Control Mode
d4: E.F. External Fault Input (N.O.)
d5: E.F. External Fault Input (N.C.)
d6: Reset
d7: Multi-Step Speed Command 1
d8: Multi-Step Speed Command 2
d9: Multi-Step Speed Command 3

d1