Chapter 8 Maintenance and Inspections|VFD-S Series

8-4

Revision August 2006, SE08, SW V2.61

DC capacity of main circuit

Maintenance

Period

Check Items

Methods and Criterion

Daily

Half

Year

One

Year

If there is any leakage of liquid,
change of color, cracks or
deformation

Visual inspection

Measure static capacity when
required

Static capacity

initial value X 0.85

Resistor of main circuit

Maintenance

Period

Check Items

Methods and Criterion

Daily

Half

Year

One

Year

If there is any peculiar smell or
insulator cracks due to
overheating

Visual inspection, smell

If there is any disconnection

Visual inspection or measure with
multimeter after removing wiring
between +1/+2 ~ -

Resistor value should be within

±

10%

Transformer and reactor of main circuit

Maintenance

Period

Check Items

Methods and Criterion

Daily

Half

Year

One

Year

If there is any abnormal vibration
or peculiar smell

Visual, aural inspection and smell

Magnetic contactor and relay of main circuit

Maintenance

Period

Check Items

Methods and Criterion

Daily

Half

Year

One

Year

If there are any loose screws

Visual and aural inspection. Tighten
screw if necessary.

Check to see if contacts work
correctly

Visual inspection