Chapter 5 Parameters|VFD-S Series

Revision August 2006, SE08, SW V2.61

5-77

This parameter selects the operation of the drive upon a loss of PID feedback signal.

A-10

Sleep Frequency

Unit: 0.1

Settings

d0.0 to d400Hz

Factory Setting: d0.0

A-11

Wakeup Frequency

Unit: 0.1

Settings

d0.0 to d400Hz

Factory Setting: d0.0

A-12

Sleep Period

Unit: 0.1

Settings

d0.0 to d650 seconds

Factory Setting: d0.0

These parameters determine sleep functions of the AC drive. If the command frequency falls

below the sleep frequency, for the specified time in Pr. A-12, then the drive will shut off the

output and wait until the command frequency rises above Pr. A-11. Please see the below

diagram.

A-11

A-10

A-12

0Hz

Sleep Function

Sleep Period

Sleep Frequency

Wakeup Frequency

Frequency Command

Actual running
output frequency

A-13

PID User Defined

Unit: 0.1

Settings

d0.0 to d400

Factory Setting: d0.0

When parameter A-13 is set to 0, what F and H display is the actual value of setting

frequency and output frequency. When this parameter is not set to 0, the display value of F

and H = actual value

¯A-13/1-00. To set frequency with panel, communication, VR, AVI or

ACI need to set according to the display value. For example, when 1-00=60.0Hz, if A-13 is set

to 30.0 Hz, it means when the actual value of frequency is 30.00 Hz, the display value will be

15.0 Hz . If you want to let drive run at 10.0Hz, the frequency command must be 5.0 Hz. But