Example 5 (Pr. 5-07 = d1 Execute one cycle of the PLC program):

In this example, the PLC program runs continuously. It should be noted that the times of reserve

motion may be shorter than expected, due to the acceleration/deceleration times.

Frequency

60Hz

50Hz

40Hz

30Hz

20Hz

15Hz

10Hz

0Hz

Time
(Sec)

FWD

REV

5-09

Master freq.=5Hz
5-00=10 Hz
5-01=20 Hz
5-02=40 Hz
5-03=60 Hz
5-04=50 Hz
5-05=30 Hz
5-06=15 Hz

4-07=d17
3-05=d10
3-06=d11
5-07=d1
5-08=d68

5-09=10
5-10=10
5-11=12
5-12

Sec
Sec

Sec

=15 Sec

5-13=15 Sec
5-14=8 Sec
5-15=17 Sec
5-16=17 Sec

* The calculation of time for Pr.5-11, Pr.5-12, Pr.5-15 and Pr.5-16 should be carefully planned.

5-08

PLC Forward/Reverse Motion

Unit: 1

Settings

d0 to d255

Factory Setting: d0

This parameter controls the direction of motion for the Multi-Step Speed Pr.5-00 to Pr.5-06

and the Master Frequency. The original direction of Master Frequency will become invalid.

NOTE

The equivalent 8-bit number is used to program the forward/reverse motion for each of the 8 speed

steps (including Master Frequency). The binary notation for the 8-bit number must be translated into

decimal notation and then be entered.

1

2

3

4

5

6

7

Weights

Bit

0=Forward

1=Reverse

Direction of 1st

Pr.5-00

speed for

Direction of 2nd

Pr.5-01

speed for

Direction of 3rd

Pr.5-02

speed for

Direction of 4th

Pr.5-03

speed for

Direction of 5

Pr.5-04

th speed for

Direction of 6

Pr.5-05

th speed for

Direction of 7

Pr.5-06

th speed for

0

Director of Master Frequency during PLC