Chapter 2 Installation and Wiring

2.1 Ambient Conditions

Install the AC motor drive in an environment with the following conditions:

Operation Air

Temperature: -10 ~ +50°C (14 ~ 122°F)

-10 ~ +40°C (14 ~ 104°F) for side-by-side
mounting

Relative Humidity:

<90%, no condensation allowed

Atmosphere pressure:

86 ~ 106 kPa

Installation Site Altitude:

<1000m

Vibration:

<20Hz: 9.80 m/s

2

(1G) max

20 ~ 50Hz: 5.88 m/s

2

(0.6G) max

Storage
Transportation

Temperature: -20°C

~

+60°C (-4°F ~ 140°F)

Relative Humidity:

<90%, no condensation allowed

Atmosphere pressure:

86 ~ 106 kPa

Vibration:

<20Hz: 9.80 m/s

2

(1G) max

20 ~ 50Hz: 5.88 m/s

2

(0.6G) max

Pollution Degree

2: good for a factory type environment.

CAUTION!

1.

Operating, storing or transporting the AC motor drive outside these conditions may cause

damage to the AC motor drive.

2.

Failure to observe these precautions may void the warranty!

2.2 Installation

1.

Mount the AC motor drive vertically on a flat vertical surface by using bolts or screws. Other

directions are not allowed.

2.

The AC motor drive will generate heat during operation. Allow sufficient space around the unit

for heat dissipation.

3.

The heat sink temperature may rise to 90°C when running. The material on which the AC motor

drive is mounted must be noncombustible and be able to withstand this high temperature.

4.

When the AC motor drive is installed in a confined space (e.g. cabinet), the surrounding

temperature must be within 10 ~ 40°C with good ventilation. DO NOT install the AC motor drive

in a space with bad ventilation.