Chapter 5 Parameters|VFD-S Series

5-72

Revision August 2006, SE08, SW V2.61

Content Address

Functions

35:

Reserved

36: PID error (Pld)
37: Reserved
38: Phase loss (PHL)

Status of AC Drive

00: RUN LED light off, STOP LED light up
01: RUN LED blink, STOP LED light up
10: RUN LED light up, STOP LED blink

Bit 0-1

11: RUN LED light up, STOP LED light off

Bit 2

01: Jog active

00: REV LED light off, FWD LED light up

01: REV LED blink, FWD LED light up
10: REV LED light up, FWD LED blink

Bit 3-4

11: REV LED light up, FRD LED light off

Bit 5-7

Not used

2101H

Bit 8

1: Main freq. Controlled by communication

Bit 9

1: Main freq. Controlled by external terminal

Bit 10

1: Operation command controlled by communication

Bit 11

1: Parameters have been locked

Bit 12-15 Not Used

2102H Frequency

command F (XXX.XX)

2103H Output

Frequency H (XXX.XX)

2104H Output

Current A (XXX.XX)

2105H DC-BUS

Voltage U (XXX.XX)

2106H Output

Voltage E (XXX.XX)

2107H

Step number of Multi-Step Speed Operation

2108H

Step number of PLC operation

2109H

Time of PLC Operation

210AH Counter

Value

3.6 Exception response:

The AC motor drive is expected to return a normal response after receiving command

messages from the master device. The following depicts the conditions when no

normal response is replied to the master device.

The AC motor drive does not receive the messages due to a communication error; thus, the AC

motor drive has no response. The master device will eventually process a timeout

condition.

The AC motor drive receives the messages without a communication error, but cannot handle

them. An exception response will be returned to the master device and an error

message “CExx” will be displayed on the keypad of AC motor drive. The xx of “CExx”

is a decimal code equal to the exception code that is described below.

In the exception response, the most significant bit of the original command code is set to 1, and

an exception code which explains the condition that caused the exception is

returned.