Group 4: Input Function Parameters

4-00

Potentiometer Bias Frequency

Unit: 0. 1

Settings

d0.0 to d100.0%

Factory Setting: d0.0

4-01

Potentiometer Bias Polarity

Factory Setting: d0

Settings

d0

Positive

Bias

d1

Negative

Bias

4-02

Potentiometer Frequency Gain

Unit: 1

Settings

d1 to d200%

Factory Setting: d100

4-03

Potentiometer Reverse Motion Enable

Factory Setting: d0

Settings

d0

Forward motion only

d1

Reverse motion enable (must be negative bias)

Pr.4-00 to Pr.4-03 are used when the source of frequency command is the analog signal (0 to

+10V DC or 4 to 20 mA DC). Refer to the following examples.

Example 1:

The following is the most common method. Set parameter 2-00 to d1 (0 to +10V signal) or d2 (4 to

20mA current signal).


Example 2:

In this example with the potentiometer set to 0V the Output Frequency is 10 Hz. The mid-point of

the potentiometer becomes 40 Hz. Once the Maximum Output Frequency is reached any further

increase of the potentiometer will not increase output frequency.