Generac Power Systems 53187 User Manual
Page 56
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
SECTION 1.9
OPERATIONAL TESTS AND ADJUSTMENTS
Voltage Regulator Adjustment (Contln>
ued)
UNITS W ITH 15 INCH STATOR (CONT’D);
14. Turn OFF all electrical loads and check the voltage
regulator lam ps at no-load.
15. W hen all adjustm ents have been com pleted, let the
engine run at no-load for a few m inutes to stabiiize
internal engine-generator tem peratures.
16. Shut the engine dow n.
I
PARTI
THE REVOLVING FIELD AC GENERATOR
Overspeed Shutdown Adjustment
GENERAL;
NP series generators are equipped w ith an auto
m atic shutdow n system w hich w ill stop the engine in
the event of an overspeed. Shutdow n w ill occur auto
m atically w hen AC frequency (engine speed) exceeds
approxim ately 69-71 Hertz (2070-2130 rpm ). Adjust
m ent of the overspeed shutdow n setting is required
w hen the unit’s engine control circuit board is replaced.
Figure 5. Engine Control Circuit Board
ADJUSTMENT PROCEDURE:
To adjust the overspeed shutdow n setting, proceed
as follow s;
1. On the engine controi circuit board, turn the OVER
SPEED
SHUTDOW N
POTENTIOMETER
counter
clockw ise until it just contacts its stop. DO NOT
FORCE.
2. Connect an accurate AC frequency m eter across the
generator’s AC output leads.
3. Start the engine, let it stabilize and w arm up.
4. Use the injection pum p throttle lever to SLOW LY
increase engine speed untii the frequency m eter reads
69-71 Hertz.
5. Hold the thrtottle at 69-71 Hertz and SLOW LY turn
the OVERSPEED SHUTDOW N POT clockw ise. W hen
the engine shuts dow n, overspeed setting is correct.
PAGE 1.9-4