PARTI
THE REVOLVING FIELD AC GENERATOR
Voltage Regulator Adjustment (Contin
ued):
SECTION 1.9
I
OPERATIONAL TESTS & ADJUSTMENTS
i
0
VOLTAGE
REGULATOR
“ +
2
6
1
4
11
22
0 0 0 0 0 0
Figure 2. Voltage Regulator (Units w ith 10" Stator)
UNITS W ITH 15 INCH STATOR:
The voltage regulator used on NP series units w ith
15 inch stator is show n in Figure 4. To adjust the
regulator, proceed as follow s:
1. Gain access to the voltage regulator in the generator
control panel.
2. If a new replacem ent regulator is being installed,
locate Sw itch ‘SW r on the regulator circuit board. Set
the sw itch to Position “2". Position "1“ is used only for
brushless generators.
3. Connect an accurate AC voltm eter and frequency
m eter to the generator’s AC output leads.
4. W ith unit shut dow n, set the voltage regulator poten
tiom eters as follow s:
a. Turn the “Voltage Adjust’' pot fully counterclock
w ise.
b. Set "Gain" to its centered or m id-position.
c. Set "Stability" to its centered or m id-position.
d. Do NOT adjust the ’’Underfrequency Adjust" pot.
5. If so equipped, set the control panel’s voltage adjust
pot to its centered or m id-position.
6. Turn OFF ail electrical loads. Startup and initial
adjustm ents w ill be accom plished under a "no-load"
condition.
7. Start the engine, let it stabilize and w arm up at
no-load.
8. Check the reading on the frequency m eter.
a. Frequency shouid be 60.5-63.5 Hertz.
b. If necessary, adjust the engine governor to obtain
a no-load frequency reading as ciose to 62 Hertz as
possible. See adjustm ent procedure for governor.
c. Do NOT' proceed until governor is properly ad
justed and frequency reading is correct.
9. Check the lam ps (LED’s) on the voltage regulator.
All lam ps should be ON. If any lam p is OUT, see
appropriate troubleshooting section.
10. Turn the reguiator's "Voltage Adjust" pot to obtain
a line-to-line voltage of 242-254 volts; a line-to-neutral
voltage of 121 -127 volts. Try to get the voltage as close
as possible to 124 volts (line-to-neutral): or 248 volts
(line-to-line).
11. If the red "Regulator" lam p is flashing, turn the
"Stability" pot either direction until the flashing stops.
12. Apply an electrical load and check engine speed
recovery.
a. Adjust the "Underfrequency Adjust" counterclock
w ise to unload the unit and reduce load voltage w hile
the engine recovers.
b. For flat regulation (no voltage decrease as fre
quency drops), turn the ’’Underfrequency Adjust"
fully clockw ise. Set point for this adjustm ent is 62
Hertz (counterclockw ise) to 52 Hertz (clockw ise).
c. To obtain a constant voltage reduction as fre
quency drops, set "Underfrequency Adjust" fully
counterclockw ise.
13. W ith electrical load still applied, check the "Regu
lator" lam p for flashing. If lam p is flashing, adjust the
"Stability" pot until flashing stops.
14. If better response is needed, adjust the "Gain" pot
clockw ise as needed. Then, if needed, correct for insta
bility by adjusting the "Stability" pot.