SECTION 1.5
THE REVOLVING FIELD AC GENERATOR ■ INTRODUCTION TO TROUBLESHOOTING
Stator AC Connection Systems (Continued)
3-PHASE DELTA STATOR W INDING:
Som e units m ay be equipped w ith a 3-phase delta
type stator w inding, show n in Figure 6. Phase rotation
is L1-L2-L3. The ^Neutral* line is designated as "LO’.
Generator Model No. 9422 uses this type of stator to
deliver 120 volts AC (line-to-neutral); or 240 volts AC
(line-to-line).
3-PHASE. W YE-CONNECTED SYSTEM:
Figure 7 show s a 3-phase W ye-Type stator w hich
has 12 AC output leads that are reconnectable to
supply several voltages. Generator Model 9318 uses
this type of statorto supply 220/380 volts AC at 50 Hertz
(i.e., 220 volts AC line-to-neutral; 380 volts AC line-to-
line).
Figure 6. A 3-Phase Delta Stator
PAGE 1.5-3
- 004709-0 (52 pages)
- GUARDIAN 04136-0 (44 pages)
- 04389-1 (60 pages)
- 1.6L 18 kW (64 pages)
- 9593-3 (36 pages)
- 005213-0 (52 pages)
- 0043733 (64 pages)
- 005337-0 (64 pages)
- 004370-2 (60 pages)
- Whisper - Test UL 2200 (4 pages)
- 2.4L (68 pages)
- 004917-2 (48 pages)
- SG025 (4 pages)
- Quietpact 55 (92 pages)
- 05176-0 (52 pages)
- 004916-0 (44 pages)
- 940-2 (144 pages)
- GUARDIAN 43734 (64 pages)
- Guardian 5410 (82 pages)
- NP-30G (126 pages)
- A-2624 (28 pages)
- Guardian 4703 (2 pages)
- 9 kW NG (192 pages)
- IM Series (36 pages)
- 005220-0 (60 pages)
- 009734-5 (60 pages)
- GUARDIAN ELITE 005053-1 (56 pages)
- 005221-0 (60 pages)
- SP SERIES (1 page)
- 0941-1 (56 pages)
- 0661-5 (48 pages)
- 004373-6 (64 pages)
- 004988-4 (48 pages)
- Transfer Switches and Accessories (15 pages)
- QT04524 (4 pages)
- 004988-1 (48 pages)
- 004917-4 (48 pages)
- 04390-1 (60 pages)
- Guardian Elite 05402 (4 pages)
- XP Series (4 pages)
- 005210-0 (56 pages)
- 04760-0 (56 pages)
- 005012-1 (48 pages)
- Q-Series (56 pages)