beautypg.com

Sens lo 5.0 flo, Flo re6, 854 sprayer control – TeeJet 854 Sprayer Control User Manual

Page 25: Sensor.selection

background image

www.teejet.com

20

854 Sprayer Control

Figure 4-17: Flow Sensor Minimum Flow Capacity

SEnS

LO

5.0

FLO

Flow Meter Rates:

Nominal Flow Meter Size

Minimum Flow Rate in GPM (l/min)

1/2”

0.79 GPM (3 l/min)

3/4”

1.9 GPM (7 l/min)

1”

2.6 GPM (10 l/min)

801-PP-RUB

2.5 GPM (9.5 l/min)

1 1/2”

9.2 GPM (35 l/min)

2”

19 GPM (72 l/min)

Sensor.Selection

NOTE: This step may not appear. It will only

appear if both sensors (pressure sensor

and flow sensor) have been installed and

programmed.

The 854 system can be used with either a flow

meter, pressure transducer, or both. The Sense

Selection step instructs the console which type(s) of

sensor is/are being used to control the regulation.

• Use the PLUS or MINUS keys to

select either “Flo” for Flow Meter or “PRS” for

Pressure Sensor.

• Press the PROGRAM key to advance to the

next step.

If both sensors are installed on the sprayer, this

process will determine which sensor is used as

the primary one for regulation. If “Flo” is selected,

the Flow Meter will be used to control flow and the

pressure transducer will be used only to display the

actual pressure. If “PRS” is selected, the pressure

transducer will be used to control the flow and

display the actual pressure.
Figure 4-18: Sensor Selection

FLO

Re6

Section.Valve.Type

The Section Valve Type distinguishes the type of On/

Off boom control valves installed on the machine.

There are 2 types of valves that can be used:

• 2-way valves
• 3-way valves

A 2-way control valve is simply an On/Off valve.

Flow is either directed to the boom section(s) or it is

blocked.
A 3-way control valve is known as a Bypass valve.

Flow continuously passes through this valve. When

the valve is activated (on), flow is directed to the

boom section(s). When the valve is not activated

(off), flow is directed through a bypass port back to

the supply tank.

• Change the value if required by pressing the

PLUS or MINUS keys.

• Press the PROGRAM key to accept the

value and advance to the next step.