Model sk5208 basic operating instructions, Sk-5208 – SilentKnight SK-5208 Conventional FACP 10-30 Zone User Manual
Page 99

Cut Along the
Dotted
Line
PN 151214 Rev B
ECN 14-00
Model SK5208 Basic Operating Instructions
These Instructions must be framed and displayed next to the
SK-5208
panel in
accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems.
LED Meanings
Operation
Task to Perform
Test the system
Press 0 ENTER them enter a code if prompted.
The system will perform a display lamp test and a communication test. Displays Firmware
Revisions.
Reset Alarms
Press 1 ENTER or RESET then enter a code if prompted.
Reset the Dialer
Press 3 ENTER, then enter a code if prompted
Resets the dialer and aborts the call to central station.
Display History Events
Press 5 ENTER then enter a code if prompted. Displays the panel history, which includes alarms,
supervisories, troubles, reports, time and date changes, etc.
Show Status
Press 6 ENTER then enter a code if prompted. View existing system status. List Alarms first,
supervisories and then troubles.
Silence Troubles or Alarms
Press 7 ENTER or SILENCE then enter a code if prompted. Silence LED will light.
Disable/Enable a Zone
1.
Press Zone # + *
2.
Enter Code. Repeat the process to enable the zone.
Disable/Enable NAC
1.
Press 1 0 NAC # + *
2.
Enter Code. Repeat the process to enable the NAC.
Conduct a Fire Drill
1.
Press 2 0 ENTER then enter a code
2.
Press RESET then code to end the drill.
Reset Detectors
1.
Press 2 1 ENTER then enter a code. Resets all smoke detector power.
Walk Test the System
1.
Press 2 2 ENTER then enter a code
2.
Press RESET to end the Walk Test.
Acknowledge Events
Events can be acknowledged by pressing the ENTER button. No code is required to
acknowledge events. The status LEDs (Alarm, Supervisory and Trouble) will flash when an un-
acknowledged alarm, supervisory, or trouble condition exists.
After each event has been acknowledged its associated LED (Alarm, Supervisory, or Trouble
LED) stop flashing and turn on steady. When viewing system status the LCD displays “Acked” for
each individual event once it has been acknowledged. The control panel piezo will silence after
all alarms have been acknowledged.
Note: The control panel piezo will continue to sound for Supervisories and Troubles even after
the event has been acknowledged. Supervisories and troubles will silence once the event
is restored.
After the event is acknowledged an event is added to the event history buffer. Acknowledged
events in the history buffer will be preceded with an asterisk “*”.
LED
Status
Condition
ALARM (red)
Off
Normal condition
On
System in alarm.
Flashing
LED will flash when a alarm condition exists that has not been acknowledged.
SUPERVISORY
(yellow)
Off
Normal condition
On
If a supervisory condition exist on the system.
Flashing
LED will flash when a supervisory condition exists that has not been
acknowledged.
TROUBLE (yellow)
Off
Normal condition
On
Trouble condition exists
Flashing
LED will flash when a trouble condition exists that has not been
acknowledged.
SILENCED (yellow)
Off
Normal condition.
On
Alarm or trouble condition has been silenced but condition still exists.
AC (green)
On
Panel is running on AC (normal condition); standby battery fully charged.
Off
Panel has lost all power.
Flashing
Panel is running on battery power only or AC power only.