Model sk5208 basic operating instructions, Sk-5208 – SilentKnight SK-5208 Conventional FACP 10-30 Zone User Manual

Page 99

background image

Cut Along the

Dotted

Line

PN 151214 Rev B

ECN 14-00

Model SK5208 Basic Operating Instructions

These Instructions must be framed and displayed next to the

SK-5208

panel in

accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems.

LED Meanings

Operation

Task to Perform

Test the system

Press 0 ENTER them enter a code if prompted.
The system will perform a display lamp test and a communication test. Displays Firmware
Revisions.

Reset Alarms

Press 1 ENTER or RESET then enter a code if prompted.

Reset the Dialer

Press 3 ENTER, then enter a code if prompted
Resets the dialer and aborts the call to central station.

Display History Events

Press 5 ENTER then enter a code if prompted. Displays the panel history, which includes alarms,
supervisories, troubles, reports, time and date changes, etc.

Show Status

Press 6 ENTER then enter a code if prompted. View existing system status. List Alarms first,
supervisories and then troubles.

Silence Troubles or Alarms

Press 7 ENTER or SILENCE then enter a code if prompted. Silence LED will light.

Disable/Enable a Zone

1.

Press Zone # + *

2.

Enter Code. Repeat the process to enable the zone.

Disable/Enable NAC

1.

Press 1 0 NAC # + *

2.

Enter Code. Repeat the process to enable the NAC.

Conduct a Fire Drill

1.

Press 2 0 ENTER then enter a code

2.

Press RESET then code to end the drill.

Reset Detectors

1.

Press 2 1 ENTER then enter a code. Resets all smoke detector power.

Walk Test the System

1.

Press 2 2 ENTER then enter a code

2.

Press RESET to end the Walk Test.

Acknowledge Events

Events can be acknowledged by pressing the ENTER button. No code is required to
acknowledge events. The status LEDs (Alarm, Supervisory and Trouble) will flash when an un-
acknowledged alarm, supervisory, or trouble condition exists.
After each event has been acknowledged its associated LED (Alarm, Supervisory, or Trouble
LED) stop flashing and turn on steady. When viewing system status the LCD displays “Acked” for
each individual event once it has been acknowledged. The control panel piezo will silence after
all alarms have been acknowledged.
Note: The control panel piezo will continue to sound for Supervisories and Troubles even after

the event has been acknowledged. Supervisories and troubles will silence once the event
is restored.

After the event is acknowledged an event is added to the event history buffer. Acknowledged
events in the history buffer will be preceded with an asterisk “*”.

LED

Status

Condition

ALARM (red)

Off

Normal condition

On

System in alarm.

Flashing

LED will flash when a alarm condition exists that has not been acknowledged.

SUPERVISORY
(yellow)

Off

Normal condition

On

If a supervisory condition exist on the system.

Flashing

LED will flash when a supervisory condition exists that has not been
acknowledged.

TROUBLE (yellow)

Off

Normal condition

On

Trouble condition exists

Flashing

LED will flash when a trouble condition exists that has not been
acknowledged.

SILENCED (yellow)

Off

Normal condition.

On

Alarm or trouble condition has been silenced but condition still exists.

AC (green)

On

Panel is running on AC (normal condition); standby battery fully charged.

Off

Panel has lost all power.

Flashing

Panel is running on battery power only or AC power only.