Model SK-5208 Installation Manual

151204

3-9

Remote Annunciator
Connections

30

SKI

Used to connect 5235 remote annunciators to the control
panel.

31

SKO

32

PWR

33

GND

Notification Appliance
Circuit 4

34

+

NAC4

3 Amp maximum per circuit. Voltage 27.4 VDC, 1.5
Ohms Maximum.

Note:

Total control panel current is 6 Amps.

35

_

Notification Appliance
Circuit 3

36

+

NAC3

37

_

Notification Appliance
Circuit 2

38

+

NAC2

39

_

Notification Appliance
Circuit 1

40

+

NAC1

41

_

Auxiliary Relay 4

42

NO

Relay contacts are rated at 2.5 A, 24 VDC/24VAC
(inductive rating). 5A, 24 VDC/24 VAC (resistive).
Connect to power limited source only.

43

COM

44

NC

Auxiliary Relay 3

45

NO

46

COM

47

NC

Auxiliary Relay 2

48

NO

49

COM

50

NC

Auxiliary Relay 1

51

NO

52

COM

53

NC

Telco Line 2

54

TIP

P2

Telephone line 2 connection terminals (see Section 3.10
for wiring diagram).

55

RING

56

TIP

T2

57

RING

Telco Line 1

58

TIP

P1

Telephone line 1 connection terminals (see Section 3.10
for wiring diagram).

59

RING

60

TIP

T1

61

RING

Table 3-4: Terminal Descriptions

Function

Terminal

Number

Terminal Label

Comments