beautypg.com

Section 6 reporting, 1 reporting formats, Reporting formats -1 – SilentKnight SK-5208 Conventional FACP 10-30 Zone User Manual

Page 75

background image

151204

6-1

Section 6
Reporting

The SK-5208 can transmit information in four different formats. This section describes the four basic reporting
formats of the SK-5208 and the codes that they send to a central station receiver. Of these four formats some of
the formats offer a more specific selection for that format. For example, you can select a 3/1 format that requires
a 1400 or 2300 Hz handshake, or SIA format that can handle 8 or 20 events per call. Selecting the correct format
depends on the type of receiver that will receive calls from the SK-5208.

The SK-5208 DACT is compatible with Silent Knight Model 9800 and 9500 Digital Receivers.

6.1

Reporting Formats

This section gives a description of each of the SK-5208 reporting formats. Refer to Table 6-1.

Table 6-1: Reporting Formats Descriptions

Format Name

Description

Category

Name

Programming

Name

3/1

3/1 14

Old format, transmits a 3-digit account number and a 1-digit event code.
Transmissions are acknowledged at 1400 Hz.

3/1 23

Old format, transmits a 3-digit account number and a 1-digit event code.
Transmissions are acknowledged at 2300 Hz.

4/2

SK4/2 1400

Tone burst format, transmits a 4-digit account code and 2-digit event code.
Transmissions are acknowledged at 1400 Hz.

SIA

SIA8

Security Industry Association standard communication format which send a
maximum of 8 events per call.

SIA20

Security Industry Association standard communication format which send a
maximum of 20 events per call. Up to a 6-digit account number.

Contact ID

Contact ID

Ademco Contact ID format. DTMF (Dual Tone Multiple Frequency) format. Send a
4-digit account number. Transmission is acknowledged at both 1400 and 2300 Hz.