beautypg.com

SilentKnight SK-5208 Conventional FACP 10-30 Zone User Manual

Page 60

background image

Model SK-5208 Installation Manual

151204

4-19

Misc System
(cont.)

5217 Expanders

1

Enables zones 11-20.

2

Enables zones 21-30

Plex Door

No

X

If Yes is selected you are not required to enter a
Code for operator level functions, such as Reset,
Silence, and Display Event History.
Note: If this option is enabled, the PLEX-2
accessory must be installed on the control panel.

Yes

NAC (1-4) # Cadence

Constant

Additional cadence patterns are programmable
only through down loading software. See also
Section 4.2.3.

March Code

ANSI S-3.41 Code

All NACs

Single Stroke BI

California Code

System Sensor Sync.

Wheelock Sync.

Gentex Sync.

Faraday Sync.

Amseco Sync.

NAC Options

Silence NAC

_ _ _ _

No NACs
selected

If number is selected that NAC may be silenced.

Fire NAC

1 2 3 4

All NACs
selected

If number is selected that NAC will activate for
any fire alarm.

Prealarm NAC

_ _ _ _

No NACs
selected

If number is selected that NAC will activate during
the prealarm timer countdown.

Aux NAC

_ _ _ _

No NACs
selected

If number is selected that NAC will activate for
undefined, heat, cold, and water alarms.

Waterflow NAC

1 2 3 4

All NACs
selected

If number is selected that NAC will activate for
waterflow alarms.

Supervisory NAC

_ _ _ _

No NACs
selected

If number is selected that NAC will activate for
sprinkler supervisories.

Crossalert A NAC

_ _ _ _

No NACs
selected

If you have a single zone, that is programmed for
crossalarm verification, in alarm, all NAC output
select for this option will activate.

Release A NAC

_ _ _ _

No NACs
selected

Activates during the group “A” releasing action.
This circuit would be connected to a UL listed
releasing solenoid. See Table 5-4 for compatible
solenoids.

Crossalert B NAC

_ _ _ _

No NACs
selected

If you have a single zone, that is programmed for
crossalarm verification, in alarm, all NAC output
select for this option will activate.

Release B

_ _ _ _

No NACs
selected

Activates during the group “B” releasing action.
This circuit would be connected to a UL listed
releasing solenoid. See Table 5-4 for compatible
solenoids.

Trouble NAC

_ _ _ _

No NACs
selected

If number is selected that NAC will activate for
any trouble condition.

Direct Conn NAC

_ _ _ _

No NACs
selected

for alarms when using the 5220 module for city
box or polarity reversal. Corresponding relay
number will automatically be selected.

NACs With EOL

1 2 3 4

All NACs
selected

If number is selected that NAC output must be
supervised with an 4.7 k

 UL listed EOL.

Table 4-4: Programming Options

Programming

Option

Menu Item

Choices

Default

Comments