SilentKnight SK-5208 Conventional FACP 10-30 Zone User Manual
Page 60

Model SK-5208 Installation Manual
151204
4-19
Misc System
(cont.)
5217 Expanders
1
Enables zones 11-20.
2
Enables zones 21-30
Plex Door
No
X
If Yes is selected you are not required to enter a
Code for operator level functions, such as Reset,
Silence, and Display Event History.
Note: If this option is enabled, the PLEX-2
accessory must be installed on the control panel.
Yes
NAC (1-4) # Cadence
Constant
Additional cadence patterns are programmable
only through down loading software. See also
Section 4.2.3.
March Code
ANSI S-3.41 Code
All NACs
Single Stroke BI
California Code
System Sensor Sync.
Wheelock Sync.
Gentex Sync.
Faraday Sync.
Amseco Sync.
NAC Options
Silence NAC
_ _ _ _
No NACs
selected
If number is selected that NAC may be silenced.
Fire NAC
1 2 3 4
All NACs
selected
If number is selected that NAC will activate for
any fire alarm.
Prealarm NAC
_ _ _ _
No NACs
selected
If number is selected that NAC will activate during
the prealarm timer countdown.
Aux NAC
_ _ _ _
No NACs
selected
If number is selected that NAC will activate for
undefined, heat, cold, and water alarms.
Waterflow NAC
1 2 3 4
All NACs
selected
If number is selected that NAC will activate for
waterflow alarms.
Supervisory NAC
_ _ _ _
No NACs
selected
If number is selected that NAC will activate for
sprinkler supervisories.
Crossalert A NAC
_ _ _ _
No NACs
selected
If you have a single zone, that is programmed for
crossalarm verification, in alarm, all NAC output
select for this option will activate.
Release A NAC
_ _ _ _
No NACs
selected
Activates during the group “A” releasing action.
This circuit would be connected to a UL listed
releasing solenoid. See Table 5-4 for compatible
solenoids.
Crossalert B NAC
_ _ _ _
No NACs
selected
If you have a single zone, that is programmed for
crossalarm verification, in alarm, all NAC output
select for this option will activate.
Release B
_ _ _ _
No NACs
selected
Activates during the group “B” releasing action.
This circuit would be connected to a UL listed
releasing solenoid. See Table 5-4 for compatible
solenoids.
Trouble NAC
_ _ _ _
No NACs
selected
If number is selected that NAC will activate for
any trouble condition.
Direct Conn NAC
_ _ _ _
No NACs
selected
for alarms when using the 5220 module for city
box or polarity reversal. Corresponding relay
number will automatically be selected.
NACs With EOL
1 2 3 4
All NACs
selected
If number is selected that NAC output must be
supervised with an 4.7 k
UL listed EOL.
Table 4-4: Programming Options
Programming
Option
Menu Item
Choices
Default
Comments