3-14

on each circuit. Figure 3-9 shows how to connect the notification circuits to the SK-5208.

Figure 3-9 Supervised Notification Appliance Wiring

3 Amp maximum current draw from any single NAC output (not to exceed a total current draw of 6 amps for the
control panel). See Appendix A for a list of the UL notification appliances that can be used with the SK-5208.
Contact Silent Knight if you have any questions about compatible notification circuits.

All circuit are regulated unless used for releasing service in which case they are considered special applications.
See Section 5.5 for details on releasing.

Supervised
Power Limited

4.7 k

UL Listed EOL

Model 7628

3 Amps Max. per circuit full
wave rectified, 27.5 VDC, 1.5
Ohms Maximum.