Agency Listings and Requirements 151204

2-2

2.2.1

Requirements for All Installations

General requirements are described below. The sections that follow describe additional requirements for the type
of installation (for example, Central Station Fire Alarm systems, Local Protected Fire Alarm systems, and so on).

1.

Use UL listed smoke detectors compatible with the SK-5208. Refer to Appendix A.

2.

Use UL listed compatible notification devices. Refer to Appendix A.

Restricted Options:

The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 - 30 hours. For UL
certified installations this number must be set from 1 to 3 hours.

Call forwarding shall not be used.

When cross zoning is used detector spacing shall be cut in half, you shall not use the alarm verification
feature, and no delay shall be used.

2.2.2

Requirements for Central Station Fire Alarm Systems

1.

The Phone Line “Line Dial Type” must be selected for anything other than “Not Used”. (See programming
Section 4.2.9).

2.

On class A (style D) zones, the number of waterflow devices is limited to five.

3.

Auxiliary relays may not be programmed to activate for Pre-Alarm. See programming Section 4.2.5.

2.2.3

Requirements for Auxiliary Protected Fire Alarm Systems

for Fire Alarm Service

1.

Follow the current load restrictions shown in Section 3.6.

2.

The Model 5220 Direct Connect module must be installed (see Section 3.15.1 for wiring).

2.2.4

Requirements for Remote Station Protected Fire Alarm

Systems, for Digital Communication or Polarity Reversal

1.

Follow the current load restrictions shown in Section 3.6.

2.

Use the SK-5208’s built-in dialer or install the Model 5220 Direct Connect Module (see Section 3.15.1).