beautypg.com

SilentKnight SK-5208 Conventional FACP 10-30 Zone User Manual

Page 61

background image

Programming 151204

4-20

NAC Options

Fire Drill NAC

1 2 3 4

All NACs
selected

If number is selected that NAC will activate during
a fire drill.

Relay Options

Silence Relay

_ _ _ _

No Relays
selected

If a relay is selected, that relay can be silenced for
Trouble and Supervisory conditions only. (This
includes relays programmed for AC Trbl.)

Fire Relay

1 _ _ _

Relay 1
selected

If a relay is selected, that relay will activate for fire
alarm conditions.

Prealarm Relay

_ _ _ _

No Relays
selected

If a relay is selected, that relay will activate for
prealarm conditions.

Aux Relay

_ _ _ _

No Relays
selected

If a relay is selected, that relay will activate for
Auxiliary conditions.

Waterflow Relay

_ _ _ _

No Relays
selected

If a relay is selected, that relay will activate for
waterflow conditions.

Superv Relay

_ _ _ _

No Relays
selected

If a relay is selected, that relay will activate for
supervisory conditions.

Crossalert A Relay _ _ _ _

No Relays
selected

If a relay is selected, that relay will activate for
crossalarm conditions.

Release A Relay

_ _ _ _

No Relays
selected

If selected will activate for releasing group “A”.

Crossalert B Relay _ _ _ _

No Relays
selected

If a relay is selected, that relay will activate for
crossalarm conditions.

Release B Relay

_ _ _ _

No Relays
selected

If selected will activate for releasing group “B”.

Trouble Relay

_ _ _ 4

X

Relay will be activated when no troubles exist and
will deactivate when a trouble condition occurs.

Fire Drill Relay

1 _ _ _

Relay 1
selected

If a relay is selected, that relay will activate for fire
drills.

AC Trbl

_ _ _ _

No Relays
selected

If a relay is selected, that relay will be activated
when AC is normal and will deactivate when a
Low AC condition exists.

User (1-10) #
Code

Code # Type

Installers

5208 and
123456

Operators

1111

Not Used

User # Code

Enter 3 to 6 digit
number

Enter any value from 001 to 999999.

Table 4-4: Programming Options

Programming

Option

Menu Item

Choices

Default

Comments