beautypg.com

3 wiring leds to outputs, 3 wiring leds to outputs -21, See figure 3-17) – SilentKnight SK-5208 Conventional FACP 10-30 Zone User Manual

Page 31

background image

Model SK-5208 Installation Manual

151204

3-21

C1 is the coil for the relay 1, C2 is the coil for relay 2, C3 and C4 are the coils for relays 3 and 4 respectively.

Figure 3-17 Relay Wiring on the SK-5280

Note: Figure 3-17 uses A7 and T7 to activate relays 3 and 4 as an example. However, any of the outputs can be

used to trip any of the relays.

3.14.3.3 Wiring LEDs to Outputs

The outputs (A1-A10 and T1-T10) can be used to operate LEDs used in a remote annunciator (see Figure 3-18).
Outputs A1-A10 are alarm outputs for the zones corresponding to those outputs. For example, if the SK-5280 is
programmed to output for zones 11-20, then outputs A1-A10 will correspond with zones 11 through 20.

Outputs T1-T10 are trouble outputs for the zones corresponding to those outputs. for example, if the SK-5280 is
programmed to output for zones 21-30, then outputs T1-T10 will correspond with zones 21-30.

Figure 3-18 LED Wiring on the SK-5280

Relay Rating
2.5A @ 30 VDC/120 VAC