beautypg.com

SilentKnight SK-5208 Conventional FACP 10-30 Zone User Manual

Page 59

background image

Programming 151204

4-18

Zone (1-30) #
Options

Verify # Options

None

X

Note:

Alarm verification feature must not

be used if the FACP is being used for releas-
ing.

Smoke

Smoke verification for zones with 2- or 4-wire
detectors. Do not use any other type of device on
this circuit if Smoke Verification is selected.

Prealarm

Activated zone will start a prealarm timer that
counts down from a user programmed value (see
Section 4.2.2 for prealarm time programming). If
the timer reaches zero before the panel is reset, a
general alarm will then be sounded.

Crossalert A

See Section 5.5.

Crossalert B

Interlock A

Interlock B

Manual Release A

See Section 5.5.

Manual Release B

Enhanced Smoke

Smoke verification for zones with 2-wire detectors
and contact type devices, such as pull stations,
used on the same circuit. If the alarm current is
greater than 78 mA, the smoke verification cycle
will not occur.

Zone # Auto Sil

No

X

Alarm sounds for this zone cannot be
automatically silenced.

Yes

Alarm sounds for this zone can be automatically
silenced.

Zone # Man Sil

No

Alarm sounds for this zone cannot be manually
silenced.

Yes

X

Alarm sounds for this zone can be manually
silenced.

Zone # NAC

_ _ _ _

Select the number of each NAC to operate with
this zone in alarm.

Zone # Relay

_ _ _ _

Select the number of each Relay to operate with
this zone in alarm.

Misc System

Prealarm Time

Enter a value from 0
to 60

40 seconds

Enter time duration for prealarm verification.

Sound Prealarm

No

No on-board or 5235 remote PZT sound for
prealarms.

Yes

X

5235 and on-board PZTs will sound for prealarms.

Auto Silence

Enter a value from 0
to 60

8 minutes

This feature selects the time in minutes in which
the NAC will automatically silence. 0 = no
automatic silence

Latch Supervise

No

X

Supervisory type zones will self restore.

Yes

Supervisory type zones must be reset after any
supervisories conditions.

Class A Zone

1

Class A.

2

5235 Keypads

_ _ _ _ _ _

Touchpad numbers that are selected here will be
supervised.

Table 4-4: Programming Options

Programming

Option

Menu Item

Choices

Default

Comments