3 programming options, Programming options -17, Table 4-4 for list of programming options – SilentKnight SK-5208 Conventional FACP 10-30 Zone User Manual
Page 58

Model SK-5208 Installation Manual
151204
4-17
4.3
Programming Options
Table 4-4 list all the programming options and the items that can be modified within those programming option
menus.
Note: Programming options that have a # in the Programming Options column have multiple programmable
components. See Section 4.1.2 for additional information.
Table 4-4: Programming Options
Programming
Option
Menu Item
Choices
Default
Comments
Zone (1-30) #
Options
Zone # Location
Programmable through SKSS downloading
software. To program through On-board or remote
annunciator:
1. Press * to activate.
2. Press Up or Down arrow to move through char-
acter set.
3. Press Left or Right arrow to move cursor to
desired character location.
4. Repeat steps 2 and 3 until location name is
entered.
5. Press Enter when the desired location name is
complete.
Zone # Type
Not Used
Fire
X
Waterflow
Supervisory
Undefined
Heat
Cold
Water
AC Delay
Will generate an AC Trouble for either an open or
shorted input. The report to the receiver will be
delayed until the AC Delay timer expires. (See
Section 4.2.10 for AC Delay Time programming.)
Ext. Reset
A shorted input will reset active alarms. This type
of zone is local only. No troubles will be reported
to the central station receiver.
Ext. Silence
A shorted input will silence alarms and troubles.
This type of zone is local only. No troubles will be
reported to the central station receiver.
Zone # Local
No
X
Zone will report when activated.
Yes
Local Zone, will not report when activated.
Zone # Disable
No
Zone cannot be bypassed.
Yes
X
Zone can be bypassed.
Zone # Response
1 Sec
X
4 sec
16 sec
40 sec